ABB / FIMER UNO-8.6-TL-OUTD-S-US-A (8.6 kW)
8.6 kW, 240 Vac transformerless Grid Support Utility Interactive Inverter with arc detector. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
8.6 kW
CEC Weighted Eff.
97%
MPPT / Max DC
200–480V / 480V
NEC 705.12 Breaker
45A @ 240V
Inverter Engineering Tools
Legacy / Replacement Reference: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | ABB / FIMER |
|---|---|
| Model Number (MPN) | UNO-8.6-TL-OUTD-S-US-A |
| Inverter Topology | String Inverter |
| Continuous AC Power (Paco) | 8.6 kW (8,600 W) |
| Nominal DC Input (Pdco) | 8,863 W |
| Nominal AC Voltage | 240 Vac (Split/Single-Phase) |
| Listed Voltage Variants | 240V, 277V |
| CEC Weighted Efficiency | 97% |
| MPPT Operating Window | 200 – 480 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 480 Vdc |
| Max DC Input Current | 23.3 A |
| Night Tare Loss | 1.4 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | Yes |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 35.8 A @ 240V |
|---|---|
| 125% Continuous Duty Current | 44.8 A |
| Minimum Standard Breaker | 45 A |
| Busbar Requirement | 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (9.46–11.61 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 24–29 panels | 9.6–11.6 kW DC |
| 440W | 22–26 panels | 9.7–11.4 kW DC |
| 550W | 17–21 panels | 9.3–11.6 kW DC |
CEC-Listed 240V Equivalents to ABB / FIMER UNO-8.6-TL-OUTD-S-US-A
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (8.6 kW String Inverter) and can be added directly to your US System Kit:
Compatible Solar Panels for ABB / FIMER UNO-8.6-TL-OUTD-S-US-A
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 6–8 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 6–8 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575 | 575 W | 53.5 V | 6–8 per string (-10°C) | Verify Pair |
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 6–8 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 6–8 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 5–6 per string (-10°C) | Verify Pair |
Engineering FAQ — ABB / FIMER UNO-8.6-TL-OUTD-S-US-A
What size circuit breaker does the ABB / FIMER UNO-8.6-TL-OUTD-S-US-A require under NEC 705.12?
At 8.6 kW continuous AC output on 240V (35.8A continuous), the 125% continuous duty rule requires a minimum 45A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the ABB / FIMER UNO-8.6-TL-OUTD-S-US-A?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 8.6 kW unit with 9.46 kW to 11.61 kW DC of solar modules without exceeding 480V cold Voc.