Interactive Solar & Storage System Kit Builder

Combine any CEC-listed US solar panel (2,800), 240V inverter (1,068), and UL 9540 battery (412). Automatically checks DC/AC ratio, NEC 690.7 cold string voltage, NEC 705.12 200A busbar limits, state energy yield, and exports a clean Bill of Materials (BOM).

Loading US-certified solar equipment catalog…

How This Kit Builder Works, Sizing Formulas & Worked Example

The System Kit Builder filters our 3,007-panel, 1,903-inverter, and 559-battery database down to US residential CEC-listed equipment so you can test real hardware combinations before requesting installer bids.

  • DC Nameplate & Roof Area: DC_kW = (Panel_STC_W × Panel_Qty) ÷ 1000, with gross roof footprint computed from module dimensions (area_m² × 10.7639 × Qty).
  • DC/AC Ratio & NEC 705.12 Backfeed Check: Compares array DC size against continuous inverter AC rating (DC_kW ÷ AC_kW) and sizes the required backfeed breaker at 125% continuous AC current (I_ac × 1.25) against a 200A/225A residential busbar.
  • State Production & 2026 Cash Economics: Multiplies DC array kW by state-level NREL Peak Sun Hours, 365 days, and a 0.78–0.81 system derate factor, then estimates annual bill savings using 2026 EIA residential utility rates and state net-metering realization (1:1 Retail vs. NEM 3.0 / Avoided Cost).

Worked Example: 9.6 kW California NEM 3.0 Solar + 13.5 kWh Battery Kit

Pairing 24× 400W CEC-listed panels (9.6 kW DC, ~490 sq ft roof) with a 7.6 kW hybrid inverter (1.26× DC/AC ratio, 40A breaker on a 200A panel) and 1× 13.5 kWh LFP battery in California (5.8 Peak Sun Hours, 31.8¢/kWh EIA avg) generates roughly 15,800 kWh/year. Adding the 13.5 kWh battery shifts afternoon solar into evening peak TOU hours, raising NEM 3.0 bill-offset realization compared to grid-tied solar alone.

Want to inspect pre-built examples first? Browse our 120 Reference US Solar & Battery Configurations or read the full Engineering Methodology.