NEC Article 220.82 Optional Method · NEC 705.12 Busbar Check

200-Amp Electrical Panel Load Simulator

Toggle your home’s 240V appliances, EV charger, heat pump, and solar backfeed breaker to test whether your existing 100A/150A/200A service passes NEC 220.82 — and check 2026 upgrade pricing by state.

Toggle Active 240V / 120V Branch BreakersClick to switch
200A PANEL UPGRADE RECOMMENDED
NEC 220.82 Demand vs. 100A Main Service151.3A / 100A (151%)
Calculated Load
151.3 A
36,320 VA @ 240V
NEC 2023 705.12 Solar Max
20A Brkr
Max 16A inverter AC · exceeds 120%
TX 200A Upgrade Est.
$2,300–$4,300
Permit + 200A panel + grounding
NEC 220.82 Line ItemCalculated VARule Applied
General Lighting + Small Appliance + Appliances20,000 VA100% of first 10 kVA + 40% of remainder
Largest HVAC Load (Cooling vs Heating)4,800 VANEC 220.82(C) non-coincident max
EV Charger (EVSE Continuous Demand)11,520 VA100% nameplate (or EVEMS load-shed option)
Total Calculated Service Demand36,320 VA (151.3A)Divided by 240V split-phase
NEC 2023 705.12 120% Opposite-End Busbar Rule Exceeded

On a 100A busbar with a 100A main breaker, maximum load-side solar backfeed is 20A breaker (16A max continuous inverter output × 1.25) at the opposite end of the bus. Options include a main breaker derate, a 225A solar-ready panel, or a supply-side tap where allowed by Oncor. Note: NEC 2026 relocates load calculations to Article 120 — verify your local AHJ adopted edition.

NEC 220.82 & NEC 705.12 Rules Used in This Simulator

  • General Loads (NEC 220.82(B)): 3 VA/sq ft living area + 3,000 VA small-appliance circuits + 1,500 VA laundry + fastened appliances. The first 10,000 VA is counted at 100%, and everything above 10,000 VA at 40%.
  • Non-Coincident HVAC (NEC 220.82(C)): Only the larger of air conditioning or electric space heating is added (you do not run central AC and resistance heat strips simultaneously).
  • Solar 120% Busbar Rule (NEC 705.12(B)(3)(2)): For load-side backfeed at the opposite end of the busbar, Main Breaker + Solar Breaker ≤ 1.20 × Busbar Rating.
Immaculate newly installed 200-amp US residential electrical panel with neatly dressed copper wiring