AIMS Power PIHY9600 (9.592 kW)
9.6 kW, 240 Vac, Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
9.592 kW
CEC Weighted Eff.
96.5%Class Estimate
MPPT / Max DC
235–480V / 480V
NEC 705.12 Breaker
50A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Electrical & Grid-Support Datasheet
| Manufacturer | AIMS Power |
|---|---|
| Model Number (MPN) | PIHY9600 |
| Inverter Topology | Hybrid Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 9.592 kW (9,592 W) |
| Nominal DC Input (Pdco) | 9,801 W |
| Nominal AC Voltage | 240 Vac (Split/Single-Phase) |
| CEC Weighted Efficiency | 96.5% (Class Estimate — Not listed in CEC) |
| MPPT Operating Window | 235 – 480 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 480 Vdc |
| Max DC Input Current | 27.2 A |
| Night Tare Loss | 0.65 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 40 A @ 240V |
|---|---|
| 125% Continuous Duty Current | 50.0 A |
| Minimum Standard Breaker | 50 A |
| Busbar Requirement | 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (10.55–12.95 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 26–32 panels | 10.4–12.8 kW DC |
| 440W | 24–29 panels | 10.6–12.8 kW DC |
| 550W | 19–24 panels | 10.4–13.2 kW DC |
Compatible Solar Panels for AIMS Power PIHY9600
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 7–8 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 7–8 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575 | 575 W | 53.5 V | 7–8 per string (-10°C) | Verify Pair |
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 7–8 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 7–8 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 5–6 per string (-10°C) | Verify Pair |
Engineering FAQ — AIMS Power PIHY9600
What size circuit breaker does the AIMS Power PIHY9600 require under NEC 705.12?
At 9.592 kW continuous AC output on 240V (40A continuous), the 125% continuous duty rule requires a minimum 50A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the AIMS Power PIHY9600?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 9.592 kW unit with 10.55 kW to 12.95 kW DC of solar modules without exceeding 480V cold Voc.