Fronius Primo GEN24 3.8 208-240 Plus (3.802 kW)
3.8 kW, 240 Vac Hybrid Grid Support Utility Interactive Inverter with arc detector, PLC transmitter, and meter. Inverter with PCS functionality. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
3.802 kW
CEC Weighted Eff.
96.5%Class Estimate
MPPT / Max DC
200–480V / 480V
NEC 705.12 Breaker
20A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Electrical & Grid-Support Datasheet
| Manufacturer | Fronius |
|---|---|
| Model Number (MPN) | Primo GEN24 3.8 208-240 Plus |
| Inverter Topology | Hybrid Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 3.802 kW (3,802 W) |
| Nominal DC Input (Pdco) | 3,904 W |
| Nominal AC Voltage | 240 Vac (Split/Single-Phase) |
| Listed Voltage Variants | 240V, 208V |
| CEC Weighted Efficiency | 96.5% (Class Estimate — Not listed in CEC) |
| MPPT Operating Window | 200 – 480 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 480 Vdc |
| Max DC Input Current | 9.8 A |
| Night Tare Loss | 8.3 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | CSA Group |
| Built-in Revenue Meter | Yes |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 15.8 A @ 240V |
|---|---|
| 125% Continuous Duty Current | 19.8 A |
| Minimum Standard Breaker | 20 A |
| Busbar Requirement | 100A Busbar (120% rule: up to 20A backfeed) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (4.18–5.13 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 10–13 panels | 4.0–5.2 kW DC |
| 440W | 10–12 panels | 4.4–5.3 kW DC |
| 550W | 8–9 panels | 4.4–5.0 kW DC |
Compatible Solar Panels for Fronius Primo GEN24 3.8 208-240 Plus
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 6–8 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 6–8 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575 | 575 W | 53.5 V | 6–8 per string (-10°C) | Verify Pair |
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 6–8 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 6–8 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 5–6 per string (-10°C) | Verify Pair |
Engineering FAQ — Fronius Primo GEN24 3.8 208-240 Plus
What size circuit breaker does the Fronius Primo GEN24 3.8 208-240 Plus require under NEC 705.12?
At 3.802 kW continuous AC output on 240V (15.8A continuous), the 125% continuous duty rule requires a minimum 20A overcurrent breaker. Busbar note: 100A Busbar (120% rule: up to 20A backfeed).
What solar array size pairs best with the Fronius Primo GEN24 3.8 208-240 Plus?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 3.802 kW unit with 4.18 kW to 5.13 kW DC of solar modules without exceeding 480V cold Voc.