GM CEC-Listed · 240V ResidentialHybridUL 1741-SB (3rd Ed.)Battery Hybrid

General Motors Energy GM Energy Inverter e1.11 (11.589 kW)

11.520 kW, 240 Vac Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .

Continuous AC Output
11.589 kW
CEC Weighted Eff.
97.5%
MPPT / Max DC
200–480V / 480V
NEC 705.12 Breaker
70A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
General Motors Energy GM Energy Inverter e1.11 — Illustrative category photo — not this exact model · Real residential hybrid/string solar inverter
Illustrative category photo — not this exact model · Real residential hybrid/string solar inverterWikimedia Commons — File:Central inverter cutout.jpg (CC0)
DC INPUT & MPPT TRACKING WINDOW (HYBRID) MPPT 200–480 Vdc 200V 480V MAX 480V PV DC INPUT ≤ 480V DC 11.589 kW · 97.5% CEC PV + BATTERY HYBRID AC OUTPUT 240V · 70A BRKR

Electrical & Grid-Support Datasheet

General Motors Energy GM Energy Inverter e1.11 Electrical and Grid-Support Specifications
ManufacturerGeneral Motors Energy
Model Number (MPN)GM Energy Inverter e1.11
Inverter TopologyHybrid Inverter (PV + Battery Hybrid)
Continuous AC Power (Paco)11.589 kW (11,589 W)
Nominal DC Input (Pdco)11,948 W
Nominal AC Voltage240 Vac (Split/Single-Phase)
Listed Voltage Variants208V, 240V
CEC Weighted Efficiency97.5%
MPPT Operating Window200 – 480 Vdc (NREL SAM Measured)
Max DC Input Voltage480 Vdc
Max DC Input Current31.4 A
Night Tare Loss16.48 W
UL 1741 Supplement SBCertified (3rd Ed.)
UL 1741 Supplement SANo
Certifying LaboratoryCSA Group
Built-in Revenue MeterNo / Optional

NEC 705.12(B) Backfeed & Panel Check

NEC 705.12 Backfeed Breaker Calculation for GM Energy Inverter e1.11
Max Continuous AC Current48.3 A @ 240V
125% Continuous Duty Current60.4 A
Minimum Standard Breaker70 A
Busbar Requirement200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11)

Recommended PV Array Pairing

Target DC/AC ratio 1.10×–1.35× (12.75–15.65 kW DC total).

Recommended Solar Panel Quantity by Wattage Class for GM Energy Inverter e1.11
Panel ClassRecommended QtyDC Array / Ratio
400W32–39 panels12.8–15.6 kW DC
440W29–36 panels12.8–15.8 kW DC
550W23–28 panels12.7–15.4 kW DC

Compatible Solar Panels for General Motors Energy GM Energy Inverter e1.11

Test any of 3,007 panels with this inverter →
Compatible Solar Panels for General Motors Energy GM Energy Inverter e1.11
Solar Panel ModelSTC PowerVoc (25°C)String / Pairing FitAction
Boviet Solar BVM7612M-580-H-HC-BF580 W52.42 V6–8 per string (-10°C)Verify Pair
SEG Solar SEG-580-BTA-HV580 W51.95 V6–8 per string (-10°C)Verify Pair
Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575575 W53.5 V6–8 per string (-10°C)Verify Pair
Mission Solar MSH10-560HN4G {A}560 W50.5 V6–8 per string (-10°C)Verify Pair
Canadian Solar CS6W-555MB-AG555 W49.8 V6–8 per string (-10°C)Verify Pair
REC Solar REC475AA Pure-RX-DC475 W65.7 V5–6 per string (-10°C)Verify Pair

Engineering FAQ — General Motors Energy GM Energy Inverter e1.11

What size circuit breaker does the General Motors Energy GM Energy Inverter e1.11 require under NEC 705.12?
At 11.589 kW continuous AC output on 240V (48.3A continuous), the 125% continuous duty rule requires a minimum 70A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the General Motors Energy GM Energy Inverter e1.11?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 11.589 kW unit with 12.75 kW to 15.65 kW DC of solar modules without exceeding 480V cold Voc.