HR CEC-Listed · 240V ResidentialHybridUL 1741-SB (3rd Ed.)Battery Hybrid

Huizhou Roypow Technology SUN10000S-U (10.111 kW)

10.111 kW, 240 Vac Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .

Continuous AC Output
10.111 kW
CEC Weighted Eff.
95.5%
MPPT / Max DC
200–440V / 440V
NEC 705.12 Breaker
60A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Huizhou Roypow Technology SUN10000S-U — Illustrative category photo — not this exact model · Real residential hybrid/string solar inverter
Illustrative category photo — not this exact model · Real residential hybrid/string solar inverterWikimedia Commons — File:Central inverter cutout.jpg (CC0)
DC INPUT & MPPT TRACKING WINDOW (HYBRID) MPPT 200–440 Vdc 200V 440V MAX 440V PV DC INPUT ≤ 440V DC 10.111 kW · 95.5% CEC PV + BATTERY HYBRID AC OUTPUT 240V · 60A BRKR

Electrical & Grid-Support Datasheet

Huizhou Roypow Technology SUN10000S-U Electrical and Grid-Support Specifications
ManufacturerHuizhou Roypow Technology
Model Number (MPN)SUN10000S-U
Inverter TopologyHybrid Inverter (PV + Battery Hybrid)
Continuous AC Power (Paco)10.111 kW (10,111 W)
Nominal DC Input (Pdco)10,589 W
Nominal AC Voltage240 Vac (Split/Single-Phase)
CEC Weighted Efficiency95.5%
MPPT Operating Window200 – 440 Vdc (NREL SAM Measured)
Max DC Input Voltage440 Vdc
Max DC Input Current35.3 A
Night Tare Loss36.53 W
UL 1741 Supplement SBCertified (3rd Ed.)
UL 1741 Supplement SANo
Certifying LaboratoryCSA Group
Built-in Revenue MeterNo / Optional

NEC 705.12(B) Backfeed & Panel Check

NEC 705.12 Backfeed Breaker Calculation for SUN10000S-U
Max Continuous AC Current42.1 A @ 240V
125% Continuous Duty Current52.6 A
Minimum Standard Breaker60 A
Busbar Requirement200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11)

Recommended PV Array Pairing

Target DC/AC ratio 1.10×–1.35× (11.12–13.65 kW DC total).

Recommended Solar Panel Quantity by Wattage Class for SUN10000S-U
Panel ClassRecommended QtyDC Array / Ratio
400W28–34 panels11.2–13.6 kW DC
440W25–31 panels11.0–13.6 kW DC
550W20–25 panels11.0–13.8 kW DC

Compatible Solar Panels for Huizhou Roypow Technology SUN10000S-U

Test any of 3,007 panels with this inverter →
Compatible Solar Panels for Huizhou Roypow Technology SUN10000S-U
Solar Panel ModelSTC PowerVoc (25°C)String / Pairing FitAction
Boviet Solar BVM7612M-580-H-HC-BF580 W52.42 V6–7 per string (-10°C)Verify Pair
SEG Solar SEG-580-BTA-HV580 W51.95 V6–7 per string (-10°C)Verify Pair
Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575575 W53.5 V6–7 per string (-10°C)Verify Pair
Mission Solar MSH10-560HN4G {A}560 W50.5 V6–8 per string (-10°C)Verify Pair
Canadian Solar CS6W-555MB-AG555 W49.8 V6–8 per string (-10°C)Verify Pair
REC Solar REC475AA Pure-RX-DC475 W65.7 V5–6 per string (-10°C)Verify Pair

Engineering FAQ — Huizhou Roypow Technology SUN10000S-U

What size circuit breaker does the Huizhou Roypow Technology SUN10000S-U require under NEC 705.12?
At 10.111 kW continuous AC output on 240V (42.1A continuous), the 125% continuous duty rule requires a minimum 60A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the Huizhou Roypow Technology SUN10000S-U?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 10.111 kW unit with 11.12 kW to 13.65 kW DC of solar modules without exceeding 440V cold Voc.

More Huizhou Roypow Technology Inverters

SUN12000S-U (12.079 kW)SUN15000S-U (14.987 kW)All Huizhou Roypow Technology Equipment →