BYD BEG500KTL-U/01 (501.756 kW)
500 kVA, 480 Vac, Grid Support Utility Interactive Battery Inverter, permanently connected, bi-directional for use with battery management system. This model does not have protective cover for cooling fans. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
501.756 kW
CEC Weighted Eff.
96%
MPPT / Max DC
780–1000V / 1000V
NEC 705.12 Breaker
800A @ 480V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | BYD |
|---|---|
| Model Number (MPN) | BEG500KTL-U/01 |
| Inverter Topology | Commercial 3-Phase Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 501.756 kW (501,756 W) |
| Nominal DC Input (Pdco) | 521,992 W |
| Nominal AC Voltage | 480 Vac (3-Phase) |
| CEC Weighted Efficiency | 96% |
| MPPT Operating Window | 780 – 1000 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 1000 Vdc |
| Max DC Input Current | 586.5 A |
| Night Tare Loss | 2 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 603.5 A @ 480V |
|---|---|
| 125% Continuous Duty Current | 754.4 A |
| Minimum Standard Breaker | 800 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (551.93–677.37 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 1380–1693 panels | 552.0–677.2 kW DC |
| 440W | 1254–1539 panels | 551.8–677.2 kW DC |
| 550W | 1004–1232 panels | 552.2–677.6 kW DC |
CEC-Listed 240V Equivalents to BYD BEG500KTL-U/01
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (501.756 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Engineering FAQ — BYD BEG500KTL-U/01
What size circuit breaker does the BYD BEG500KTL-U/01 require under NEC 705.12?
At 501.756 kW continuous AC output on 480V (603.5A continuous), the 125% continuous duty rule requires a minimum 800A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the BYD BEG500KTL-U/01?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 501.756 kW unit with 551.93 kW to 677.37 kW DC of solar modules without exceeding 1000V cold Voc.