Canadian Solar CSI-185K-T600GL02-U (185.005 kW)
185 kW, 600 Vac Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
185.005 kW
CEC Weighted Eff.
98.5%
MPPT / Max DC
850–1300V / 1300V
NEC 705.12 Breaker
225A @ 600V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Canadian Solar |
|---|---|
| Model Number (MPN) | CSI-185K-T600GL02-U |
| Inverter Topology | Commercial 3-Phase Inverter |
| Continuous AC Power (Paco) | 185.005 kW (185,005 W) |
| Nominal DC Input (Pdco) | 188,214 W |
| Nominal AC Voltage | 600 Vac (3-Phase) |
| CEC Weighted Efficiency | 98.5% |
| MPPT Operating Window | 850 – 1300 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 1300 Vdc |
| Max DC Input Current | 174.3 A |
| Night Tare Loss | 1 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 178 A @ 600V |
|---|---|
| 125% Continuous Duty Current | 222.5 A |
| Minimum Standard Breaker | 225 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (203.51–249.76 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 509–624 panels | 203.6–249.6 kW DC |
| 440W | 463–568 panels | 203.7–249.9 kW DC |
| 550W | 370–454 panels | 203.5–249.7 kW DC |
CEC-Listed 240V Equivalents to Canadian Solar CSI-185K-T600GL02-U
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (185.005 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for Canadian Solar CSI-185K-T600GL02-U
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 23–23 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 23–23 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-550MB-AG | 550 W | 49.6 V | 24–24 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 18–18 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.TRON BLK M-G2.D+ 445 | 445 W | 40.16 V | 30–30 per string (-10°C) | Verify Pair |
| Silfab Solar SIL-540XM | 540 W | 47.95 V | 24–24 per string (-10°C) | Verify Pair |
Engineering FAQ — Canadian Solar CSI-185K-T600GL02-U
What size circuit breaker does the Canadian Solar CSI-185K-T600GL02-U require under NEC 705.12?
At 185.005 kW continuous AC output on 600V (178A continuous), the 125% continuous duty rule requires a minimum 225A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Canadian Solar CSI-185K-T600GL02-U?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 185.005 kW unit with 203.51 kW to 249.76 kW DC of solar modules without exceeding 1300V cold Voc.