Canadian Solar CSI-50KTL-GS (50 kW)
50 kW, 480 Vac, 3-phase Grid Support Utility Interactive Inverter,. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
50 kW
CEC Weighted Eff.
98.5%
MPPT / Max DC
580–720V / 720V
NEC 705.12 Breaker
80A @ 480V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Canadian Solar |
|---|---|
| Model Number (MPN) | CSI-50KTL-GS |
| Inverter Topology | Commercial 3-Phase Inverter |
| Continuous AC Power (Paco) | 50 kW (50,000 W) |
| Nominal DC Input (Pdco) | 50,800 W |
| Nominal AC Voltage | 480 Vac (3-Phase) |
| CEC Weighted Efficiency | 98.5% |
| MPPT Operating Window | 580 – 720 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 720 Vdc |
| Max DC Input Current | 78.2 A |
| Night Tare Loss | 1 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 60.1 A @ 480V |
|---|---|
| 125% Continuous Duty Current | 75.1 A |
| Minimum Standard Breaker | 80 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (55–67.5 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 138–169 panels | 55.2–67.6 kW DC |
| 440W | 125–153 panels | 55.0–67.3 kW DC |
| 550W | 100–123 panels | 55.0–67.7 kW DC |
CEC-Listed 240V Equivalents to Canadian Solar CSI-50KTL-GS
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (50 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Engineering FAQ — Canadian Solar CSI-50KTL-GS
What size circuit breaker does the Canadian Solar CSI-50KTL-GS require under NEC 705.12?
At 50 kW continuous AC output on 480V (60.1A continuous), the 125% continuous duty rule requires a minimum 80A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Canadian Solar CSI-50KTL-GS?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 50 kW unit with 55 kW to 67.5 kW DC of solar modules without exceeding 720V cold Voc.