Delta Electronics E8 Plus-TL-US(AC) (7.72 kW)
7680 W, 240 Vac Transformerless Grid Support Utility Interactive Energy Storage Inverter with PCS functionality. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
7.72 kW
CEC Weighted Eff.
98%
MPPT / Max DC
350–480V / 480V
NEC 705.12 Breaker
45A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Electrical & Grid-Support Datasheet
| Manufacturer | Delta Electronics |
|---|---|
| Model Number (MPN) | E8 Plus-TL-US(AC) |
| Inverter Topology | Hybrid Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 7.72 kW (7,720 W) |
| Nominal DC Input (Pdco) | 7,880 W |
| Nominal AC Voltage | 240 Vac (Split/Single-Phase) |
| Listed Voltage Variants | 208V, 240V |
| CEC Weighted Efficiency | 98% |
| MPPT Operating Window | 350 – 480 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 480 Vdc |
| Max DC Input Current | 19.7 A |
| Night Tare Loss | 3.21 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | CSA Group |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 32.2 A @ 240V |
|---|---|
| 125% Continuous Duty Current | 40.3 A |
| Minimum Standard Breaker | 45 A |
| Busbar Requirement | 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (8.49–10.42 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 21–26 panels | 8.4–10.4 kW DC |
| 440W | 19–24 panels | 8.4–10.6 kW DC |
| 550W | 15–19 panels | 8.3–10.4 kW DC |
Engineering FAQ — Delta Electronics E8 Plus-TL-US(AC)
What size circuit breaker does the Delta Electronics E8 Plus-TL-US(AC) require under NEC 705.12?
At 7.72 kW continuous AC output on 240V (32.2A continuous), the 125% continuous duty rule requires a minimum 45A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the Delta Electronics E8 Plus-TL-US(AC)?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 7.72 kW unit with 8.49 kW to 10.42 kW DC of solar modules without exceeding 480V cold Voc.