DL CEC-Listed · 240V ResidentialHybridUL 1741-SB (3rd Ed.)Battery Hybrid

Delta Electronics E8 Plus-TL-US(AC) (7.72 kW)

7680 W, 240 Vac Transformerless Grid Support Utility Interactive Energy Storage Inverter with PCS functionality. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .

Continuous AC Output
7.72 kW
CEC Weighted Eff.
98%
MPPT / Max DC
350–480V / 480V
NEC 705.12 Breaker
45A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Delta Electronics E8 Plus-TL-US(AC) — Illustrative category photo — not this exact model · Real residential hybrid/string solar inverter
Illustrative category photo — not this exact model · Real residential hybrid/string solar inverterWikimedia Commons — File:Central inverter cutout.jpg (CC0)
DC INPUT & MPPT TRACKING WINDOW (HYBRID) MPPT 350–480 Vdc 350V 480V MAX 480V PV DC INPUT ≤ 480V DC 7.72 kW · 98% CEC PV + BATTERY HYBRID AC OUTPUT 240V · 45A BRKR

Electrical & Grid-Support Datasheet

Delta Electronics E8 Plus-TL-US(AC) Electrical and Grid-Support Specifications
ManufacturerDelta Electronics
Model Number (MPN)E8 Plus-TL-US(AC)
Inverter TopologyHybrid Inverter (PV + Battery Hybrid)
Continuous AC Power (Paco)7.72 kW (7,720 W)
Nominal DC Input (Pdco)7,880 W
Nominal AC Voltage240 Vac (Split/Single-Phase)
Listed Voltage Variants208V, 240V
CEC Weighted Efficiency98%
MPPT Operating Window350 – 480 Vdc (NREL SAM Measured)
Max DC Input Voltage480 Vdc
Max DC Input Current19.7 A
Night Tare Loss3.21 W
UL 1741 Supplement SBCertified (3rd Ed.)
UL 1741 Supplement SACertified
Certifying LaboratoryCSA Group
Built-in Revenue MeterNo / Optional

NEC 705.12(B) Backfeed & Panel Check

NEC 705.12 Backfeed Breaker Calculation for E8 Plus-TL-US(AC)
Max Continuous AC Current32.2 A @ 240V
125% Continuous Duty Current40.3 A
Minimum Standard Breaker45 A
Busbar Requirement200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11)

Recommended PV Array Pairing

Target DC/AC ratio 1.10×–1.35× (8.49–10.42 kW DC total).

Recommended Solar Panel Quantity by Wattage Class for E8 Plus-TL-US(AC)
Panel ClassRecommended QtyDC Array / Ratio
400W21–26 panels8.4–10.4 kW DC
440W19–24 panels8.4–10.6 kW DC
550W15–19 panels8.3–10.4 kW DC

Engineering FAQ — Delta Electronics E8 Plus-TL-US(AC)

What size circuit breaker does the Delta Electronics E8 Plus-TL-US(AC) require under NEC 705.12?
At 7.72 kW continuous AC output on 240V (32.2A continuous), the 125% continuous duty rule requires a minimum 45A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the Delta Electronics E8 Plus-TL-US(AC)?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 7.72 kW unit with 8.49 kW to 10.42 kW DC of solar modules without exceeding 480V cold Voc.

More Delta Electronics Inverters

E8-TL-US (7.68 kW)M8-TL-US (7.68 kW)E8_BDI (7.716 kW)M10-TL-US (9.62 kW)E10-TL-US(AC) (9.632 kW)E10_BDI (9.674 kW)All Delta Electronics Equipment →