Go Electric 250-480-60-HLT (259.2 kW)
250 kW, 480 Vac Grid Support Multi-Mode Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
259.2 kW
CEC Weighted Eff.
93%
MPPT / Max DC
540–780V / 780V
NEC 705.12 Breaker
400A @ 480V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Go Electric |
|---|---|
| Model Number (MPN) | 250-480-60-HLT |
| Inverter Topology | Commercial 3-Phase Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 259.2 kW (259,200 W) |
| Nominal DC Input (Pdco) | 274,787 W |
| Nominal AC Voltage | 480 Vac (3-Phase) |
| CEC Weighted Efficiency | 93% |
| MPPT Operating Window | 540 – 780 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 780 Vdc |
| Max DC Input Current | 392.6 A |
| Night Tare Loss | 748.7 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 311.8 A @ 480V |
|---|---|
| 125% Continuous Duty Current | 389.8 A |
| Minimum Standard Breaker | 400 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (285.12–349.92 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 713–875 panels | 285.2–350.0 kW DC |
| 440W | 648–795 panels | 285.1–349.8 kW DC |
| 550W | 518–636 panels | 284.9–349.8 kW DC |
CEC-Listed 240V Equivalents to Go Electric 250-480-60-HLT
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (259.2 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Engineering FAQ — Go Electric 250-480-60-HLT
What size circuit breaker does the Go Electric 250-480-60-HLT require under NEC 705.12?
At 259.2 kW continuous AC output on 480V (311.8A continuous), the 125% continuous duty rule requires a minimum 400A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Go Electric 250-480-60-HLT?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 259.2 kW unit with 285.12 kW to 349.92 kW DC of solar modules without exceeding 780V cold Voc.