GoodWe official logoCEC-Listed · 240V ResidentialHybridUL 1741-SB (3rd Ed.)Battery Hybrid

GoodWe GEH11.4-1U-US20 (11.379 kW)

11.4 kW, 240 Vac, Bi-directional, Transformerless Grid Support Utility Interactive PV and Battery Inverter, with PCS functionality. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .

Continuous AC Output
11.379 kW
CEC Weighted Eff.
97%
MPPT / Max DC
270–500V / 500V
NEC 705.12 Breaker
60A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
GoodWe GEH11.4-1U-US20 — Illustrative category photo — not this exact model · Real residential hybrid/string solar inverter
Illustrative category photo — not this exact model · Real residential hybrid/string solar inverterWikimedia Commons — File:Central inverter cutout.jpg (CC0)
DC INPUT & MPPT TRACKING WINDOW (HYBRID) MPPT 270–500 Vdc 270V 500V MAX 500V PV DC INPUT ≤ 500V DC 11.379 kW · 97% CEC PV + BATTERY HYBRID AC OUTPUT 240V · 60A BRKR

Electrical & Grid-Support Datasheet

GoodWe GEH11.4-1U-US20 Electrical and Grid-Support Specifications
ManufacturerGoodWe
Model Number (MPN)GEH11.4-1U-US20
Inverter TopologyHybrid Inverter (PV + Battery Hybrid)
Continuous AC Power (Paco)11.379 kW (11,379 W)
Nominal DC Input (Pdco)11,768 W
Nominal AC Voltage240 Vac (Split/Single-Phase)
CEC Weighted Efficiency97%
MPPT Operating Window270 – 500 Vdc (NREL SAM Measured)
Max DC Input Voltage500 Vdc
Max DC Input Current30.2 A
Night Tare Loss5.62 W
UL 1741 Supplement SBCertified (3rd Ed.)
UL 1741 Supplement SANo
Certifying LaboratoryCSA Group
Built-in Revenue MeterNo / Optional

NEC 705.12(B) Backfeed & Panel Check

NEC 705.12 Backfeed Breaker Calculation for GEH11.4-1U-US20
Max Continuous AC Current47.4 A @ 240V
125% Continuous Duty Current59.3 A
Minimum Standard Breaker60 A
Busbar Requirement200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11)

Recommended PV Array Pairing

Target DC/AC ratio 1.10×–1.35× (12.52–15.36 kW DC total).

Recommended Solar Panel Quantity by Wattage Class for GEH11.4-1U-US20
Panel ClassRecommended QtyDC Array / Ratio
400W31–38 panels12.4–15.2 kW DC
440W28–35 panels12.3–15.4 kW DC
550W23–28 panels12.7–15.4 kW DC

Compatible Solar Panels for GoodWe GEH11.4-1U-US20

Test any of 3,007 panels with this inverter →
Compatible Solar Panels for GoodWe GEH11.4-1U-US20
Solar Panel ModelSTC PowerVoc (25°C)String / Pairing FitAction
Boviet Solar BVM7612M-580-H-HC-BF580 W52.42 V8–8 per string (-10°C)Verify Pair
SEG Solar SEG-580-BTA-HV580 W51.95 V8–8 per string (-10°C)Verify Pair
Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575575 W53.5 V8–8 per string (-10°C)Verify Pair
Mission Solar MSH10-560HN4G {A}560 W50.5 V8–9 per string (-10°C)Verify Pair
Canadian Solar CS6W-555MB-AG555 W49.8 V8–9 per string (-10°C)Verify Pair
REC Solar REC475AA Pure-RX-DC475 W65.7 V6–7 per string (-10°C)Verify Pair

Engineering FAQ — GoodWe GEH11.4-1U-US20

What size circuit breaker does the GoodWe GEH11.4-1U-US20 require under NEC 705.12?
At 11.379 kW continuous AC output on 240V (47.4A continuous), the 125% continuous duty rule requires a minimum 60A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the GoodWe GEH11.4-1U-US20?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 11.379 kW unit with 12.52 kW to 15.36 kW DC of solar modules without exceeding 500V cold Voc.

More GoodWe Inverters

GW9600A-BP (9.616 kW)GW9600A-ES (9.628 kW)GW9600A-MS (9.628 kW)GW11K4-ES-US20 (11.379 kW)GEC11.4-1U-US20 (11.392 kW)GEP11.4-1-US30 (11.397 kW)All GoodWe Equipment →