Huawei FusionSolar SUN2000-6KTL-L1 (6 kW)
6 kW, 230V 50Hz Hybrid Inverter (IEC 62109 / EN 50549 (EU/Global 50Hz)). Registry source: Manufacturer IEC Datasheet (Global Reference) · CEC listing date: · Registry snapshot: .
Continuous AC Output
6 kW
CEC Weighted Eff.
97.6%
MPPT / Max DC
90–560V / 600V
NEC 705.12 Breaker
35A @ 230V
Inverter Engineering Tools
Global / Non-US Reference: Designed for non-US 50Hz / 230V–400V grids; not UL 1741-SB listed for US interconnection.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Huawei FusionSolar |
|---|---|
| Model Number (MPN) | SUN2000-6KTL-L1 |
| Inverter Topology | Hybrid Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 6 kW (6,000 W) |
| Nominal DC Input (Pdco) | 6,148 W |
| Nominal AC Voltage | 230 Vac (Split/Single-Phase) |
| CEC Weighted Efficiency | 97.6% |
| MPPT Operating Window | 90 – 560 Vdc (Manufacturer IEC Datasheet) |
| Max DC Input Voltage | 600 Vdc |
| Max DC Input Current | 12.5 A |
| Night Tare Loss | 2 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | No |
| Certifying Laboratory | IEC 62109 / EN 50549 (EU/Global 50Hz) |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 26.1 A @ 230V |
|---|---|
| 125% Continuous Duty Current | 32.6 A |
| Minimum Standard Breaker | 35 A |
| Busbar Requirement | 200A Busbar (120% rule: up to 40A backfeed) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (6.6–8.1 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 17–20 panels | 6.8–8.0 kW DC |
| 440W | 15–18 panels | 6.6–7.9 kW DC |
| 550W | 12–15 panels | 6.6–8.3 kW DC |
CEC-Listed 240V Equivalents to Huawei FusionSolar SUN2000-6KTL-L1
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (6 kW Hybrid Inverter) and can be added directly to your US System Kit:
Compatible Solar Panels for Huawei FusionSolar SUN2000-6KTL-L1
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 3–10 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 3–10 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575 | 575 W | 53.5 V | 3–10 per string (-10°C) | Verify Pair |
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 3–10 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 3–11 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 2–8 per string (-10°C) | Verify Pair |
Engineering FAQ — Huawei FusionSolar SUN2000-6KTL-L1
What size circuit breaker does the Huawei FusionSolar SUN2000-6KTL-L1 require under NEC 705.12?
At 6 kW continuous AC output on 230V (26.1A continuous), the 125% continuous duty rule requires a minimum 35A overcurrent breaker. Busbar note: 200A Busbar (120% rule: up to 40A backfeed).
What solar array size pairs best with the Huawei FusionSolar SUN2000-6KTL-L1?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 6 kW unit with 6.6 kW to 8.1 kW DC of solar modules without exceeding 600V cold Voc.