LeadSolar Energy LS600X (0.708 kW)
700 W, 240 Vac Grid Support Utility Interactive Microinverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
0.708 kW
CEC Weighted Eff.
96%
MPPT / Max DC
50–64V / 64V
NEC 705.12 Breaker
15A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Electrical & Grid-Support Datasheet
| Manufacturer | LeadSolar Energy |
|---|---|
| Model Number (MPN) | LS600X |
| Inverter Topology | Microinverter |
| Continuous AC Power (Paco) | 0.708 kW (708 W) |
| Nominal DC Input (Pdco) | 734 W |
| Nominal AC Voltage | 240 Vac (Split/Single-Phase) |
| CEC Weighted Efficiency | 96% |
| MPPT Operating Window | 50 – 64 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 64 Vdc |
| Max DC Input Current | 12.9 A |
| Night Tare Loss | 0.16 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 3 A @ 240V |
|---|---|
| 125% Continuous Duty Current | 3.8 A |
| Minimum Standard Breaker | 15 A |
| Busbar Requirement | 100A Busbar (120% rule: up to 20A backfeed) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (0.78–0.96 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 1 panel | 1:1 pairing (0.56× DC/AC) |
| 440W | 1 panel | 1:1 pairing (0.62× DC/AC) |
| 550W | 1 panel | 1:1 pairing (0.78× DC/AC) |
Engineering FAQ — LeadSolar Energy LS600X
What size circuit breaker does the LeadSolar Energy LS600X require under NEC 705.12?
At 0.708 kW continuous AC output on 240V (3A continuous), the 125% continuous duty rule requires a minimum 15A overcurrent breaker. Busbar note: 100A Busbar (120% rule: up to 20A backfeed).
What solar array size pairs best with the LeadSolar Energy LS600X?
As a 708W microinverter, it pairs 1:1 with panels rated roughly 743W to 1027W STC.