Qcells (Hanwha) Q.HOME+ AC-G1-7.6 (7.832 kW)
7.6 kW, 240 Vac, single-phase, battery, grid support utility interactive inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
7.832 kW
CEC Weighted Eff.
95.5%
MPPT / Max DC
320–430V / 430V
NEC 705.12 Breaker
45A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Electrical & Grid-Support Datasheet
| Manufacturer | Qcells (Hanwha) |
|---|---|
| Model Number (MPN) | Q.HOME+ AC-G1-7.6 |
| Inverter Topology | Hybrid Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 7.832 kW (7,832 W) |
| Nominal DC Input (Pdco) | 8,223 W |
| Nominal AC Voltage | 240 Vac (Split/Single-Phase) |
| CEC Weighted Efficiency | 95.5% |
| MPPT Operating Window | 320 – 430 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 430 Vdc |
| Max DC Input Current | 21.9 A |
| Night Tare Loss | 49.5 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | CSA Group |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 32.6 A @ 240V |
|---|---|
| 125% Continuous Duty Current | 40.8 A |
| Minimum Standard Breaker | 45 A |
| Busbar Requirement | 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (8.62–10.57 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 22–26 panels | 8.8–10.4 kW DC |
| 440W | 20–24 panels | 8.8–10.6 kW DC |
| 550W | 16–19 panels | 8.8–10.4 kW DC |
Engineering FAQ — Qcells (Hanwha) Q.HOME+ AC-G1-7.6
What size circuit breaker does the Qcells (Hanwha) Q.HOME+ AC-G1-7.6 require under NEC 705.12?
At 7.832 kW continuous AC output on 240V (32.6A continuous), the 125% continuous duty rule requires a minimum 45A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the Qcells (Hanwha) Q.HOME+ AC-G1-7.6?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 7.832 kW unit with 8.62 kW to 10.57 kW DC of solar modules without exceeding 430V cold Voc.