SP CEC-Listed · 240V ResidentialHybridUL 1741-SB (3rd Ed.)Battery Hybrid

Savant Power PS-INV-10KW-100A-XX (9.923 kW)

10 kW, 240 Vac Transformerless Grid Support Utility Interactive Hybrid Inverter, where XX are two characters, and with PCS functionality. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .

Continuous AC Output
9.923 kW
CEC Weighted Eff.
94%
MPPT / Max DC
250–530V / 530V
NEC 705.12 Breaker
60A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Savant Power PS-INV-10KW-100A-XX — Illustrative category photo — not this exact model · Real residential hybrid/string solar inverter
Illustrative category photo — not this exact model · Real residential hybrid/string solar inverterWikimedia Commons — File:Central inverter cutout.jpg (CC0)
DC INPUT & MPPT TRACKING WINDOW (HYBRID) MPPT 250–530 Vdc 250V 530V MAX 530V PV DC INPUT ≤ 530V DC 9.923 kW · 94% CEC PV + BATTERY HYBRID AC OUTPUT 240V · 60A BRKR

Electrical & Grid-Support Datasheet

Savant Power PS-INV-10KW-100A-XX Electrical and Grid-Support Specifications
ManufacturerSavant Power
Model Number (MPN)PS-INV-10KW-100A-XX
Inverter TopologyHybrid Inverter (PV + Battery Hybrid)
Continuous AC Power (Paco)9.923 kW (9,923 W)
Nominal DC Input (Pdco)10,512 W
Nominal AC Voltage240 Vac (Split/Single-Phase)
CEC Weighted Efficiency94%
MPPT Operating Window250 – 530 Vdc (NREL SAM Measured)
Max DC Input Voltage530 Vdc
Max DC Input Current29.2 A
Night Tare Loss21.92 W
UL 1741 Supplement SBCertified (3rd Ed.)
UL 1741 Supplement SACertified
Certifying LaboratoryIntertek
Built-in Revenue MeterNo / Optional

NEC 705.12(B) Backfeed & Panel Check

NEC 705.12 Backfeed Breaker Calculation for PS-INV-10KW-100A-XX
Max Continuous AC Current41.3 A @ 240V
125% Continuous Duty Current51.6 A
Minimum Standard Breaker60 A
Busbar Requirement200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11)

Recommended PV Array Pairing

Target DC/AC ratio 1.10×–1.35× (10.92–13.4 kW DC total).

Recommended Solar Panel Quantity by Wattage Class for PS-INV-10KW-100A-XX
Panel ClassRecommended QtyDC Array / Ratio
400W27–34 panels10.8–13.6 kW DC
440W25–30 panels11.0–13.2 kW DC
550W20–24 panels11.0–13.2 kW DC

Compatible Solar Panels for Savant Power PS-INV-10KW-100A-XX

Test any of 3,007 panels with this inverter →
Compatible Solar Panels for Savant Power PS-INV-10KW-100A-XX
Solar Panel ModelSTC PowerVoc (25°C)String / Pairing FitAction
Boviet Solar BVM7612M-580-H-HC-BF580 W52.42 V7–9 per string (-10°C)Verify Pair
SEG Solar SEG-580-BTA-HV580 W51.95 V7–9 per string (-10°C)Verify Pair
Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575575 W53.5 V7–9 per string (-10°C)Verify Pair
Mission Solar MSH10-560HN4G {A}560 W50.5 V7–9 per string (-10°C)Verify Pair
Canadian Solar CS6W-555MB-AG555 W49.8 V7–9 per string (-10°C)Verify Pair
REC Solar REC475AA Pure-RX-DC475 W65.7 V6–7 per string (-10°C)Verify Pair

Engineering FAQ — Savant Power PS-INV-10KW-100A-XX

What size circuit breaker does the Savant Power PS-INV-10KW-100A-XX require under NEC 705.12?
At 9.923 kW continuous AC output on 240V (41.3A continuous), the 125% continuous duty rule requires a minimum 60A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the Savant Power PS-INV-10KW-100A-XX?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 9.923 kW unit with 10.92 kW to 13.4 kW DC of solar modules without exceeding 530V cold Voc.

More Savant Power Inverters

PS-INV-10KW-60A-XX (9.923 kW)PS-INV-12.5KW-60A-XX (12.411 kW)All Savant Power Equipment →