SK CEC-Listed · 240V ResidentialHybridUL 1741-SB (3rd Ed.)Battery Hybrid

Shenzhen Kstar New Energy Company E8KD (8.024 kW)

8 kW, 240 Vac, Bi-directional, Transformerless Grid Support Utility Interactive PV and Battery Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .

Continuous AC Output
8.024 kW
CEC Weighted Eff.
97.5%
MPPT / Max DC
200–400V / 400V
NEC 705.12 Breaker
45A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Shenzhen Kstar New Energy Company E8KD — Illustrative category photo — not this exact model · Real residential hybrid/string solar inverter
Illustrative category photo — not this exact model · Real residential hybrid/string solar inverterWikimedia Commons — File:Central inverter cutout.jpg (CC0)
DC INPUT & MPPT TRACKING WINDOW (HYBRID) MPPT 200–400 Vdc 200V 400V MAX 400V PV DC INPUT ≤ 400V DC 8.024 kW · 97.5% CEC PV + BATTERY HYBRID AC OUTPUT 240V · 45A BRKR

Electrical & Grid-Support Datasheet

Shenzhen Kstar New Energy Company E8KD Electrical and Grid-Support Specifications
ManufacturerShenzhen Kstar New Energy Company
Model Number (MPN)E8KD
Inverter TopologyHybrid Inverter (PV + Battery Hybrid)
Continuous AC Power (Paco)8.024 kW (8,024 W)
Nominal DC Input (Pdco)8,278 W
Nominal AC Voltage240 Vac (Split/Single-Phase)
CEC Weighted Efficiency97.5%
MPPT Operating Window200 – 400 Vdc (NREL SAM Measured)
Max DC Input Voltage400 Vdc
Max DC Input Current27.6 A
Night Tare Loss20.79 W
UL 1741 Supplement SBCertified (3rd Ed.)
UL 1741 Supplement SANo
Certifying LaboratoryCSA Group
Built-in Revenue MeterNo / Optional

NEC 705.12(B) Backfeed & Panel Check

NEC 705.12 Backfeed Breaker Calculation for E8KD
Max Continuous AC Current33.4 A @ 240V
125% Continuous Duty Current41.8 A
Minimum Standard Breaker45 A
Busbar Requirement200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11)

Recommended PV Array Pairing

Target DC/AC ratio 1.10×–1.35× (8.83–10.83 kW DC total).

Recommended Solar Panel Quantity by Wattage Class for E8KD
Panel ClassRecommended QtyDC Array / Ratio
400W22–27 panels8.8–10.8 kW DC
440W20–25 panels8.8–11.0 kW DC
550W16–20 panels8.8–11.0 kW DC

Compatible Solar Panels for Shenzhen Kstar New Energy Company E8KD

Test any of 3,007 panels with this inverter →
Compatible Solar Panels for Shenzhen Kstar New Energy Company E8KD
Solar Panel ModelSTC PowerVoc (25°C)String / Pairing FitAction
Boviet Solar BVM7612M-580-H-HC-BF580 W52.42 V6–7 per string (-10°C)Verify Pair
SEG Solar SEG-580-BTA-HV580 W51.95 V6–7 per string (-10°C)Verify Pair
Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575575 W53.5 V6–6 per string (-10°C)Verify Pair
Mission Solar MSH10-560HN4G {A}560 W50.5 V6–7 per string (-10°C)Verify Pair
Canadian Solar CS6W-555MB-AG555 W49.8 V6–7 per string (-10°C)Verify Pair
REC Solar REC475AA Pure-RX-DC475 W65.7 V5–5 per string (-10°C)Verify Pair

Engineering FAQ — Shenzhen Kstar New Energy Company E8KD

What size circuit breaker does the Shenzhen Kstar New Energy Company E8KD require under NEC 705.12?
At 8.024 kW continuous AC output on 240V (33.4A continuous), the 125% continuous duty rule requires a minimum 45A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the Shenzhen Kstar New Energy Company E8KD?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 8.024 kW unit with 8.83 kW to 10.83 kW DC of solar modules without exceeding 400V cold Voc.

More Shenzhen Kstar New Energy Company Inverters

E10KD (10.036 kW)E12KD (12.02 kW)E15KD (14.993 kW)All Shenzhen Kstar New Energy Company Equipment →