Shenzhen Sinexcel Electric PWS1-1725KTL-H-NA-8M8 (1710.71 kW)
1725 kW, 690 Vac Grid Support Utility-Interactive Energy Storage lnverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
1710.71 kW
CEC Weighted Eff.
93%
MPPT / Max DC
1080–1450V / 1450V
NEC 705.12 Breaker
1800A @ 690V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Shenzhen Sinexcel Electric |
|---|---|
| Model Number (MPN) | PWS1-1725KTL-H-NA-8M8 |
| Inverter Topology | Commercial 3-Phase Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 1710.71 kW (1,710,710 W) |
| Nominal DC Input (Pdco) | 1,843,470 W |
| Nominal AC Voltage | 690 Vac (3-Phase) |
| CEC Weighted Efficiency | 93% |
| MPPT Operating Window | 1080 – 1450 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 1450 Vdc |
| Max DC Input Current | 1418.1 A |
| Night Tare Loss | 310.06 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | No |
| Certifying Laboratory | Intertek |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 1431.5 A @ 690V |
|---|---|
| 125% Continuous Duty Current | 1789.4 A |
| Minimum Standard Breaker | 1800 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (1881.78–2309.46 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 4704–5774 panels | 1881.6–2309.6 kW DC |
| 440W | 4277–5249 panels | 1881.9–2309.6 kW DC |
| 550W | 3421–4199 panels | 1881.5–2309.4 kW DC |
CEC-Listed 240V Equivalents to Shenzhen Sinexcel Electric PWS1-1725KTL-H-NA-8M8
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (1710.71 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Engineering FAQ — Shenzhen Sinexcel Electric PWS1-1725KTL-H-NA-8M8
What size circuit breaker does the Shenzhen Sinexcel Electric PWS1-1725KTL-H-NA-8M8 require under NEC 705.12?
At 1710.71 kW continuous AC output on 690V (1431.5A continuous), the 125% continuous duty rule requires a minimum 1800A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Shenzhen Sinexcel Electric PWS1-1725KTL-H-NA-8M8?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 1710.71 kW unit with 1881.78 kW to 2309.46 kW DC of solar modules without exceeding 1450V cold Voc.