SMA Solar SBSE9.6-US-50 (9.569 kW)
9.6 kW, 240Vac Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
9.569 kW
CEC Weighted Eff.
97.5%
MPPT / Max DC
168–480V / 480V
NEC 705.12 Breaker
50A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Electrical & Grid-Support Datasheet
| Manufacturer | SMA Solar |
|---|---|
| Model Number (MPN) | SBSE9.6-US-50 |
| Inverter Topology | Hybrid Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 9.569 kW (9,569 W) |
| Nominal DC Input (Pdco) | 9,832 W |
| Nominal AC Voltage | 240 Vac (Split/Single-Phase) |
| Listed Voltage Variants | 208V, 240V |
| CEC Weighted Efficiency | 97.5% |
| MPPT Operating Window | 168 – 480 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 480 Vdc |
| Max DC Input Current | 24.9 A |
| Night Tare Loss | 11.02 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | No |
| Certifying Laboratory | Intertek |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 39.9 A @ 240V |
|---|---|
| 125% Continuous Duty Current | 49.9 A |
| Minimum Standard Breaker | 50 A |
| Busbar Requirement | 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (10.53–12.92 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 26–32 panels | 10.4–12.8 kW DC |
| 440W | 24–29 panels | 10.6–12.8 kW DC |
| 550W | 19–23 panels | 10.4–12.7 kW DC |
Compatible Solar Panels for SMA Solar SBSE9.6-US-50
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 5–8 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 5–8 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575 | 575 W | 53.5 V | 5–8 per string (-10°C) | Verify Pair |
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 5–8 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 5–8 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 4–6 per string (-10°C) | Verify Pair |
Engineering FAQ — SMA Solar SBSE9.6-US-50
What size circuit breaker does the SMA Solar SBSE9.6-US-50 require under NEC 705.12?
At 9.569 kW continuous AC output on 240V (39.9A continuous), the 125% continuous duty rule requires a minimum 50A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the SMA Solar SBSE9.6-US-50?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 9.569 kW unit with 10.53 kW to 12.92 kW DC of solar modules without exceeding 480V cold Voc.