Solaria PowerXT-355R-AC (0.29 kW)
355 W Monocrystalline ACPV Module. DC Module: Solaria PowerXT-355R-PD. Microinverter IQ7PLUS-72-x-ACM-US {240V}. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
0.29 kW
CEC Weighted Eff.
97%
MPPT / Max DC
27–45V / 45V
NEC 705.12 Breaker
15A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Electrical & Grid-Support Datasheet
| Manufacturer | Solaria |
|---|---|
| Model Number (MPN) | PowerXT-355R-AC |
| Inverter Topology | Microinverter |
| Continuous AC Power (Paco) | 0.29 kW (290 W) |
| Nominal DC Input (Pdco) | 299 W |
| Nominal AC Voltage | 240 Vac (Split/Single-Phase) |
| CEC Weighted Efficiency | 97% |
| MPPT Operating Window | 27 – 45 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 45 Vdc |
| Max DC Input Current | 8.3 A |
| Night Tare Loss | 0.03 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 1.2 A @ 240V |
|---|---|
| 125% Continuous Duty Current | 1.5 A |
| Minimum Standard Breaker | 15 A |
| Busbar Requirement | 100A Busbar (120% rule: up to 20A backfeed) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (0.32–0.39 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 1 panel | 1:1 pairing (1.38× DC/AC) |
| 440W | 1 panel | 1:1 pairing (1.52× DC/AC) |
| 550W | 1 panel | 1:1 pairing (1.90× DC/AC) |
Compatible Solar Panels for Solaria PowerXT-355R-AC
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Mission Solar MSX10-460HN0B {C} | 460 W | 39.3 V | DC/AC 1.59 (1 panel/input) | Verify Pair |
| Trina Solar TSM-460NEG9RH.25 | 460 W | 36.3 V | DC/AC 1.59 (1 panel/input) | Verify Pair |
| SEG Solar SEG-460-BTD-HV | 460 W | 39.94 V | DC/AC 1.59 (1 panel/input) | Verify Pair |
| Qcells (Hanwha) Q.TRON BLK M-G2.D+ 445 | 445 W | 40.16 V | DC/AC 1.53 (1 panel/input) | Verify Pair |
| REC Solar REC440AA Pure-RX-DC | 440 W | 65.6 V | DC/AC 1.52 (1 panel/input) | Verify Pair |
| Canadian Solar CS6.2-48TM-460H | 460 W | 36.2 V | DC/AC 1.59 (1 panel/input) | Verify Pair |
Engineering FAQ — Solaria PowerXT-355R-AC
What size circuit breaker does the Solaria PowerXT-355R-AC require under NEC 705.12?
At 0.29 kW continuous AC output on 240V (1.2A continuous), the 125% continuous duty rule requires a minimum 15A overcurrent breaker. Busbar note: 100A Busbar (120% rule: up to 20A backfeed).
What solar array size pairs best with the Solaria PowerXT-355R-AC?
As a 290W microinverter, it pairs 1:1 with panels rated roughly 305W to 421W STC.