10 kW, 240 Vac Grid Support Utility Interactive Hybrid Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
10.008 kW
CEC Weighted Eff.
96.5%Class Estimate
MPPT / Max DC
275–450V / 450V
NEC 705.12 Breaker
60A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Electrical & Grid-Support Datasheet
| Manufacturer | SRNE Solar |
|---|---|
| Model Number (MPN) | HESP48100U200-H |
| Inverter Topology | Hybrid Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 10.008 kW (10,008 W) |
| Nominal DC Input (Pdco) | 10,509 W |
| Nominal AC Voltage | 240 Vac (Split/Single-Phase) |
| Listed Voltage Variants | 208V, 240V |
| CEC Weighted Efficiency | 96.5% (Class Estimate — Not listed in CEC) |
| MPPT Operating Window | 275 – 450 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 450 Vdc |
| Max DC Input Current | 29 A |
| Night Tare Loss | 73.6 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | No |
| Certifying Laboratory | Intertek |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 41.7 A @ 240V |
|---|---|
| 125% Continuous Duty Current | 52.1 A |
| Minimum Standard Breaker | 60 A |
| Busbar Requirement | 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (11.01–13.51 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 28–34 panels | 11.2–13.6 kW DC |
| 440W | 25–31 panels | 11.0–13.6 kW DC |
| 550W | 20–25 panels | 11.0–13.8 kW DC |
Compatible Solar Panels for SRNE Solar HESP48100U200-H
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 8–8 per string (-10°C) | Verify Pair |
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 8–8 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 8–8 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 6–6 per string (-10°C) | Verify Pair |
| Trina Solar TSM-460NEG9RH.25 | 460 W | 36.3 V | 11–11 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.TRON BLK M-G2.D+ 445 | 445 W | 40.16 V | 10–10 per string (-10°C) | Verify Pair |
Engineering FAQ — SRNE Solar HESP48100U200-H
What size circuit breaker does the SRNE Solar HESP48100U200-H require under NEC 705.12?
At 10.008 kW continuous AC output on 240V (41.7A continuous), the 125% continuous duty rule requires a minimum 60A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the SRNE Solar HESP48100U200-H?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 10.008 kW unit with 11.01 kW to 13.51 kW DC of solar modules without exceeding 450V cold Voc.