Yaskawa Solectria SGI 500XTM (507 kW)
500 kW, 1000 Vdc, 380 Vac, 3-Phase Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
507 kW
CEC Weighted Eff.
96.5%Class Estimate
MPPT / Max DC
545–820V / 820V
NEC 705.12 Breaker
1000A @ 380V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Yaskawa Solectria |
|---|---|
| Model Number (MPN) | SGI 500XTM |
| Inverter Topology | Commercial 3-Phase Inverter |
| Continuous AC Power (Paco) | 507 kW (507,000 W) |
| Nominal DC Input (Pdco) | 522,637 W |
| Nominal AC Voltage | 380 Vac (3-Phase) |
| CEC Weighted Efficiency | 96.5% (Class Estimate — Not listed in CEC) |
| MPPT Operating Window | 545 – 820 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 820 Vdc |
| Max DC Input Current | 849.8 A |
| Night Tare Loss | 88.78 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 770.3 A @ 380V |
|---|---|
| 125% Continuous Duty Current | 962.9 A |
| Minimum Standard Breaker | 1000 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (557.7–684.45 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 1394–1711 panels | 557.6–684.4 kW DC |
| 440W | 1268–1556 panels | 557.9–684.6 kW DC |
| 550W | 1014–1244 panels | 557.7–684.2 kW DC |
CEC-Listed 240V Equivalents to Yaskawa Solectria SGI 500XTM
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (507 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for Yaskawa Solectria SGI 500XTM
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 15–15 per string (-10°C) | Verify Pair |
| SEG Solar SEG-515-BTC-BG | 515 W | 47.03 V | 16–16 per string (-10°C) | Verify Pair |
| Boviet Solar BVM7610M-490-H-HC-BF | 490 W | 44.58 V | 17–17 per string (-10°C) | Verify Pair |
| Canadian Solar CS6.2-48TM-460H | 460 W | 36.2 V | 21–21 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.PEAK DUO XL-G9 470 | 470 W | 53.33 V | 14–14 per string (-10°C) | Verify Pair |
| REC Solar REC450AA 72 | 450 W | 53.2 V | 14–14 per string (-10°C) | Verify Pair |
Engineering FAQ — Yaskawa Solectria SGI 500XTM
What size circuit breaker does the Yaskawa Solectria SGI 500XTM require under NEC 705.12?
At 507 kW continuous AC output on 380V (770.3A continuous), the 125% continuous duty rule requires a minimum 1000A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Yaskawa Solectria SGI 500XTM?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 507 kW unit with 557.7 kW to 684.45 kW DC of solar modules without exceeding 820V cold Voc.