Yaskawa Solectria XGI 1500-225-600-DCG (225 kW)
225 kW, 600 Vac, Grid-Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
225 kW
CEC Weighted Eff.
98.5%
MPPT / Max DC
860–1250V / 1250V
NEC 705.12 Breaker
300A @ 600V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Yaskawa Solectria |
|---|---|
| Model Number (MPN) | XGI 1500-225-600-DCG |
| Inverter Topology | Commercial 3-Phase Inverter |
| Continuous AC Power (Paco) | 225 kW (225,000 W) |
| Nominal DC Input (Pdco) | 228,850 W |
| Nominal AC Voltage | 600 Vac (3-Phase) |
| CEC Weighted Efficiency | 98.5% |
| MPPT Operating Window | 860 – 1250 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 1250 Vdc |
| Max DC Input Current | 228.8 A |
| Night Tare Loss | 0.33 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | No |
| Certifying Laboratory | TUV Rheinland |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 216.5 A @ 600V |
|---|---|
| 125% Continuous Duty Current | 270.6 A |
| Minimum Standard Breaker | 300 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (247.5–303.75 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 619–759 panels | 247.6–303.6 kW DC |
| 440W | 563–690 panels | 247.7–303.6 kW DC |
| 550W | 450–552 panels | 247.5–303.6 kW DC |
CEC-Listed 240V Equivalents to Yaskawa Solectria XGI 1500-225-600-DCG
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (225 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Engineering FAQ — Yaskawa Solectria XGI 1500-225-600-DCG
What size circuit breaker does the Yaskawa Solectria XGI 1500-225-600-DCG require under NEC 705.12?
At 225 kW continuous AC output on 600V (216.5A continuous), the 125% continuous duty rule requires a minimum 300A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Yaskawa Solectria XGI 1500-225-600-DCG?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 225 kW unit with 247.5 kW to 303.75 kW DC of solar modules without exceeding 1250V cold Voc.