Canadian Solar CSI-25K-T480GL01-UB (24.958 kW)
25 kW, 480 Vac, Long Separate Wiring Box, Three-Phase Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
24.958 kW
CEC Weighted Eff.
98.5%
MPPT / Max DC
347–800V / 800V
NEC 705.12 Breaker
40A @ 480V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Canadian Solar |
|---|---|
| Model Number (MPN) | CSI-25K-T480GL01-UB |
| Inverter Topology | Commercial 3-Phase Inverter |
| Continuous AC Power (Paco) | 24.958 kW (24,958 W) |
| Nominal DC Input (Pdco) | 25,378 W |
| Nominal AC Voltage | 480 Vac (3-Phase) |
| CEC Weighted Efficiency | 98.5% |
| MPPT Operating Window | 347 – 800 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 800 Vdc |
| Max DC Input Current | 54 A |
| Night Tare Loss | 1 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 30 A @ 480V |
|---|---|
| 125% Continuous Duty Current | 37.5 A |
| Minimum Standard Breaker | 40 A |
| Busbar Requirement | 200A Busbar (120% rule: up to 40A backfeed) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (27.45–33.69 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 69–84 panels | 27.6–33.6 kW DC |
| 440W | 62–77 panels | 27.3–33.9 kW DC |
| 550W | 50–61 panels | 27.5–33.5 kW DC |
CEC-Listed 240V Equivalents to Canadian Solar CSI-25K-T480GL01-UB
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (24.958 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for Canadian Solar CSI-25K-T480GL01-UB
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 10–14 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 10–14 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575 | 575 W | 53.5 V | 10–13 per string (-10°C) | Verify Pair |
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 10–14 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 10–14 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 8–11 per string (-10°C) | Verify Pair |
Engineering FAQ — Canadian Solar CSI-25K-T480GL01-UB
What size circuit breaker does the Canadian Solar CSI-25K-T480GL01-UB require under NEC 705.12?
At 24.958 kW continuous AC output on 480V (30A continuous), the 125% continuous duty rule requires a minimum 40A overcurrent breaker. Busbar note: 200A Busbar (120% rule: up to 40A backfeed).
What solar array size pairs best with the Canadian Solar CSI-25K-T480GL01-UB?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 24.958 kW unit with 27.45 kW to 33.69 kW DC of solar modules without exceeding 800V cold Voc.