Canadian Solar CSI-25KTL-GS-FLB (25 kW)
25 kW, 480 Vac, 3-phase Grid Support Utility Interactive Inverter, with seperable wiring box. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
25 kW
CEC Weighted Eff.
98%
MPPT / Max DC
580–770V / 770V
NEC 705.12 Breaker
40A @ 480V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Canadian Solar |
|---|---|
| Model Number (MPN) | CSI-25KTL-GS-FLB |
| Inverter Topology | Commercial 3-Phase Inverter |
| Continuous AC Power (Paco) | 25 kW (25,000 W) |
| Nominal DC Input (Pdco) | 25,568 W |
| Nominal AC Voltage | 480 Vac (3-Phase) |
| CEC Weighted Efficiency | 98% |
| MPPT Operating Window | 580 – 770 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 770 Vdc |
| Max DC Input Current | 39.3 A |
| Night Tare Loss | 14 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 30.1 A @ 480V |
|---|---|
| 125% Continuous Duty Current | 37.6 A |
| Minimum Standard Breaker | 40 A |
| Busbar Requirement | 200A Busbar (120% rule: up to 40A backfeed) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (27.5–33.75 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 69–84 panels | 27.6–33.6 kW DC |
| 440W | 63–77 panels | 27.7–33.9 kW DC |
| 550W | 50–61 panels | 27.5–33.5 kW DC |
CEC-Listed 240V Equivalents to Canadian Solar CSI-25KTL-GS-FLB
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (25 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Engineering FAQ — Canadian Solar CSI-25KTL-GS-FLB
What size circuit breaker does the Canadian Solar CSI-25KTL-GS-FLB require under NEC 705.12?
At 25 kW continuous AC output on 480V (30.1A continuous), the 125% continuous duty rule requires a minimum 40A overcurrent breaker. Busbar note: 200A Busbar (120% rule: up to 40A backfeed).
What solar array size pairs best with the Canadian Solar CSI-25KTL-GS-FLB?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 25 kW unit with 27.5 kW to 33.75 kW DC of solar modules without exceeding 770V cold Voc.