CPS (Chint Power Systems) ECB125KTL-M/US-480 (125 kW)
125 kVA, 1000 Vdc, 480 Vac, 3-phase, Bi-directional Transformerless Grid Support Utility Interactive Battery Inverter with PCS functionality. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
125 kW
CEC Weighted Eff.
97.5%
MPPT / Max DC
750–1100V / 1100V
NEC 705.12 Breaker
200A @ 480V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | CPS (Chint Power Systems) |
|---|---|
| Model Number (MPN) | ECB125KTL-M/US-480 |
| Inverter Topology | Commercial 3-Phase Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 125 kW (125,000 W) |
| Nominal DC Input (Pdco) | 128,603 W |
| Nominal AC Voltage | 480 Vac (3-Phase) |
| CEC Weighted Efficiency | 97.5% |
| MPPT Operating Window | 750 – 1100 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 1100 Vdc |
| Max DC Input Current | 139 A |
| Night Tare Loss | 5.8 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | CSA Group |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 150.4 A @ 480V |
|---|---|
| 125% Continuous Duty Current | 188.0 A |
| Minimum Standard Breaker | 200 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (137.5–168.75 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 344–422 panels | 137.6–168.8 kW DC |
| 440W | 313–384 panels | 137.7–169.0 kW DC |
| 550W | 250–307 panels | 137.5–168.8 kW DC |
CEC-Listed 240V Equivalents to CPS (Chint Power Systems) ECB125KTL-M/US-480
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (125 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for CPS (Chint Power Systems) ECB125KTL-M/US-480
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Silfab Solar SIL-540XM | 540 W | 47.95 V | 21–21 per string (-10°C) | Verify Pair |
| REC Solar REC450AA 72 | 450 W | 53.2 V | 19–19 per string (-10°C) | Verify Pair |
| Maxeon / SunPower SPR-MAX3-425-COM-R | 425 W | 40.66 V | 25–25 per string (-10°C) | Verify Pair |
Engineering FAQ — CPS (Chint Power Systems) ECB125KTL-M/US-480
What size circuit breaker does the CPS (Chint Power Systems) ECB125KTL-M/US-480 require under NEC 705.12?
At 125 kW continuous AC output on 480V (150.4A continuous), the 125% continuous duty rule requires a minimum 200A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the CPS (Chint Power Systems) ECB125KTL-M/US-480?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 125 kW unit with 137.5 kW to 168.75 kW DC of solar modules without exceeding 1100V cold Voc.