CPS (Chint Power Systems) SCA36KTL-DO/US (36 kW)
36 kVA, 480 Vac, 1000 Vdc, 3-phase, non-isolated Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
36 kW
CEC Weighted Eff.
98%
MPPT / Max DC
540–800V / 800V
NEC 705.12 Breaker
60A @ 480V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | CPS (Chint Power Systems) |
|---|---|
| Model Number (MPN) | SCA36KTL-DO/US |
| Inverter Topology | Commercial 3-Phase Inverter |
| Continuous AC Power (Paco) | 36 kW (36,000 W) |
| Nominal DC Input (Pdco) | 36,702 W |
| Nominal AC Voltage | 480 Vac (3-Phase) |
| CEC Weighted Efficiency | 98% |
| MPPT Operating Window | 540 – 800 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 800 Vdc |
| Max DC Input Current | 50.3 A |
| Night Tare Loss | Not reported in CEC |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | Yes |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 43.3 A @ 480V |
|---|---|
| 125% Continuous Duty Current | 54.1 A |
| Minimum Standard Breaker | 60 A |
| Busbar Requirement | 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (39.6–48.6 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 99–122 panels | 39.6–48.8 kW DC |
| 440W | 90–110 panels | 39.6–48.4 kW DC |
| 550W | 72–88 panels | 39.6–48.4 kW DC |
CEC-Listed 240V Equivalents to CPS (Chint Power Systems) SCA36KTL-DO/US
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (36 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for CPS (Chint Power Systems) SCA36KTL-DO/US
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Canadian Solar CS6.2-48TM-460H | 460 W | 36.2 V | 21–21 per string (-10°C) | Verify Pair |
| Boviet Solar BVM7609M-435-H-HC-BF | 435 W | 39.23 V | 19–19 per string (-10°C) | Verify Pair |
| REC Solar REC430AA Pure 2 | 430 W | 49 V | 15–15 per string (-10°C) | Verify Pair |
| Maxeon / SunPower SPR-MAX3-435-COM | 435 W | 81.4 V | 9–9 per string (-10°C) | Verify Pair |
Engineering FAQ — CPS (Chint Power Systems) SCA36KTL-DO/US
What size circuit breaker does the CPS (Chint Power Systems) SCA36KTL-DO/US require under NEC 705.12?
At 36 kW continuous AC output on 480V (43.3A continuous), the 125% continuous duty rule requires a minimum 60A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the CPS (Chint Power Systems) SCA36KTL-DO/US?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 36 kW unit with 39.6 kW to 48.6 kW DC of solar modules without exceeding 800V cold Voc.