CPS (Chint Power Systems) SCH320KTL-DO/US-800 (320 kW)
320kVA Grid Support Utility Interactive Inverter, 1500Vdc, 800Vac 3 Phase Non-isolated. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
320 kW
CEC Weighted Eff.
98.5%
MPPT / Max DC
880–1300V / 1300V
NEC 705.12 Breaker
300A @ 800V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | CPS (Chint Power Systems) |
|---|---|
| Model Number (MPN) | SCH320KTL-DO/US-800 |
| Inverter Topology | Commercial 3-Phase Inverter |
| Continuous AC Power (Paco) | 320 kW (320,000 W) |
| Nominal DC Input (Pdco) | 325,545 W |
| Nominal AC Voltage | 800 Vac (3-Phase) |
| CEC Weighted Efficiency | 98.5% |
| MPPT Operating Window | 880 – 1300 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 1300 Vdc |
| Max DC Input Current | 273.6 A |
| Night Tare Loss | 15 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | CSA Group |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 230.9 A @ 800V |
|---|---|
| 125% Continuous Duty Current | 288.6 A |
| Minimum Standard Breaker | 300 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (352–432 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 880–1080 panels | 352.0–432.0 kW DC |
| 440W | 800–982 panels | 352.0–432.1 kW DC |
| 550W | 640–785 panels | 352.0–431.8 kW DC |
CEC-Listed 240V Equivalents to CPS (Chint Power Systems) SCH320KTL-DO/US-800
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (320 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for CPS (Chint Power Systems) SCH320KTL-DO/US-800
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 23–23 per string (-10°C) | Verify Pair |
| Canadian Solar CS6.2-48TM-460H | 460 W | 36.2 V | 34–34 per string (-10°C) | Verify Pair |
| REC Solar REC430AA Pure 2 | 430 W | 49 V | 24–24 per string (-10°C) | Verify Pair |
| SEG Solar SEG-570-BMA-TB | 570 W | 50 V | 24–24 per string (-10°C) | Verify Pair |
| Maxeon / SunPower SPR-MAX3-435-COM-R | 435 W | 40.7 V | 29–29 per string (-10°C) | Verify Pair |
Engineering FAQ — CPS (Chint Power Systems) SCH320KTL-DO/US-800
What size circuit breaker does the CPS (Chint Power Systems) SCH320KTL-DO/US-800 require under NEC 705.12?
At 320 kW continuous AC output on 800V (230.9A continuous), the 125% continuous duty rule requires a minimum 300A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the CPS (Chint Power Systems) SCH320KTL-DO/US-800?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 320 kW unit with 352 kW to 432 kW DC of solar modules without exceeding 1300V cold Voc.