CPS (Chint Power Systems) SCA50K-T-US-208 (50 kW)
50 kVA, 208 Vac, Grid Support Utility Interactive Inverter, 1000 Vdc, 3 Phase Non-isolated. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
50 kW
CEC Weighted Eff.
96.5%Class Estimate
MPPT / Max DC
200–700V / 700V
NEC 705.12 Breaker
175A @ 208V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | CPS (Chint Power Systems) |
|---|---|
| Model Number (MPN) | SCA50K-T-US-208 |
| Inverter Topology | Commercial 3-Phase Inverter |
| Continuous AC Power (Paco) | 50 kW (50,000 W) |
| Nominal DC Input (Pdco) | 52,123 W |
| Nominal AC Voltage | 208 Vac (3-Phase) |
| CEC Weighted Efficiency | 96.5% (Class Estimate — Not listed in CEC) |
| MPPT Operating Window | 200 – 700 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 700 Vdc |
| Max DC Input Current | 137.2 A |
| Night Tare Loss | 20 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | CSA Group |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 138.8 A @ 208V |
|---|---|
| 125% Continuous Duty Current | 173.5 A |
| Minimum Standard Breaker | 175 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (55–67.5 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 138–169 panels | 55.2–67.6 kW DC |
| 440W | 125–153 panels | 55.0–67.3 kW DC |
| 550W | 100–123 panels | 55.0–67.7 kW DC |
CEC-Listed 240V Equivalents to CPS (Chint Power Systems) SCA50K-T-US-208
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (50 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for CPS (Chint Power Systems) SCA50K-T-US-208
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 6–12 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 6–12 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575 | 575 W | 53.5 V | 6–11 per string (-10°C) | Verify Pair |
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 6–12 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 6–12 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 5–9 per string (-10°C) | Verify Pair |
Engineering FAQ — CPS (Chint Power Systems) SCA50K-T-US-208
What size circuit breaker does the CPS (Chint Power Systems) SCA50K-T-US-208 require under NEC 705.12?
At 50 kW continuous AC output on 208V (138.8A continuous), the 125% continuous duty rule requires a minimum 175A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the CPS (Chint Power Systems) SCA50K-T-US-208?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 50 kW unit with 55 kW to 67.5 kW DC of solar modules without exceeding 700V cold Voc.