Delta Electronics EPCS-1500US (1509.889 kW)
1500 kW, 600 Vac, 3-phase bi-directional Grid Support Utility Interactive Inverter with PCS functionality. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
1509.889 kW
CEC Weighted Eff.
98%
MPPT / Max DC
893–1500V / 1500V
NEC 705.12 Breaker
1900A @ 600V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Delta Electronics |
|---|---|
| Model Number (MPN) | EPCS-1500US |
| Inverter Topology | Commercial 3-Phase Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 1509.889 kW (1,509,889 W) |
| Nominal DC Input (Pdco) | 1,540,320 W |
| Nominal AC Voltage | 600 Vac (3-Phase) |
| CEC Weighted Efficiency | 98% |
| MPPT Operating Window | 893 – 1500 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 1500 Vdc |
| Max DC Input Current | 1184.9 A |
| Night Tare Loss | 46.13 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | No |
| Certifying Laboratory | CSA Group |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 1452.9 A @ 600V |
|---|---|
| 125% Continuous Duty Current | 1816.1 A |
| Minimum Standard Breaker | 1900 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (1660.88–2038.35 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 4152–5096 panels | 1660.8–2038.4 kW DC |
| 440W | 3775–4633 panels | 1661.0–2038.5 kW DC |
| 550W | 3020–3706 panels | 1661.0–2038.3 kW DC |
CEC-Listed 240V Equivalents to Delta Electronics EPCS-1500US
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (1509.889 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for Delta Electronics EPCS-1500US
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 24–26 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 24–26 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575 | 575 W | 53.5 V | 24–25 per string (-10°C) | Verify Pair |
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 25–27 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 25–27 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 19–21 per string (-10°C) | Verify Pair |
Engineering FAQ — Delta Electronics EPCS-1500US
What size circuit breaker does the Delta Electronics EPCS-1500US require under NEC 705.12?
At 1509.889 kW continuous AC output on 600V (1452.9A continuous), the 125% continuous duty rule requires a minimum 1900A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Delta Electronics EPCS-1500US?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 1509.889 kW unit with 1660.88 kW to 2038.35 kW DC of solar modules without exceeding 1500V cold Voc.