Delta Electronics PCS125HV (124.312 kW)
125 kW, 480 Vac, Bi-directional, Transformerless Grid support Utility Interactive Inverter with PCS functionality. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
124.312 kW
CEC Weighted Eff.
98%
MPPT / Max DC
815–1250V / 1250V
NEC 705.12 Breaker
200A @ 480V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Delta Electronics |
|---|---|
| Model Number (MPN) | PCS125HV |
| Inverter Topology | Commercial 3-Phase Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 124.312 kW (124,312 W) |
| Nominal DC Input (Pdco) | 127,304 W |
| Nominal AC Voltage | 480 Vac (3-Phase) |
| CEC Weighted Efficiency | 98% |
| MPPT Operating Window | 815 – 1250 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 1250 Vdc |
| Max DC Input Current | 134 A |
| Night Tare Loss | 19 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | No |
| Certifying Laboratory | CSA Group |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 149.5 A @ 480V |
|---|---|
| 125% Continuous Duty Current | 186.9 A |
| Minimum Standard Breaker | 200 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (136.74–167.82 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 342–420 panels | 136.8–168.0 kW DC |
| 440W | 311–381 panels | 136.8–167.6 kW DC |
| 550W | 249–305 panels | 136.9–167.8 kW DC |
CEC-Listed 240V Equivalents to Delta Electronics PCS125HV
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (124.312 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for Delta Electronics PCS125HV
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 22–22 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 22–22 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 23–23 per string (-10°C) | Verify Pair |
| Mission Solar MSX10-460HN0B {C} | 460 W | 39.3 V | 29–29 per string (-10°C) | Verify Pair |
| Trina Solar TSM-460NEG9RH.25 | 460 W | 36.3 V | 31–31 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.TRON BLK M-G2.D+ 415 | 415 W | 38.47 V | 30–30 per string (-10°C) | Verify Pair |
Engineering FAQ — Delta Electronics PCS125HV
What size circuit breaker does the Delta Electronics PCS125HV require under NEC 705.12?
At 124.312 kW continuous AC output on 480V (149.5A continuous), the 125% continuous duty rule requires a minimum 200A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Delta Electronics PCS125HV?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 124.312 kW unit with 136.74 kW to 167.82 kW DC of solar modules without exceeding 1250V cold Voc.