EPC Power 50-100A-BCDEF-G (499.13 kW)
500 kVA, 480 Vac, 3 phase, 3 wire, Bi-directional Grid Support Utility Interactive Battery Inverter, where A=099, B=61-64 or 81-84, C=A or B or D or Z, D=1-3, E=A or B, F=1 or 3, G=Re or EX or N. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
499.13 kW
CEC Weighted Eff.
97%
MPPT / Max DC
710–1250V / 1250V
NEC 705.12 Breaker
800A @ 480V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | EPC Power |
|---|---|
| Model Number (MPN) | 50-100A-BCDEF-G |
| Inverter Topology | Commercial 3-Phase Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 499.13 kW (499,130 W) |
| Nominal DC Input (Pdco) | 514,346 W |
| Nominal AC Voltage | 480 Vac (3-Phase) |
| CEC Weighted Efficiency | 97% |
| MPPT Operating Window | 710 – 1250 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 1250 Vdc |
| Max DC Input Current | 541.4 A |
| Night Tare Loss | 20 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 600.4 A @ 480V |
|---|---|
| 125% Continuous Duty Current | 750.5 A |
| Minimum Standard Breaker | 800 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (549.04–673.83 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 1373–1685 panels | 549.2–674.0 kW DC |
| 440W | 1248–1531 panels | 549.1–673.6 kW DC |
| 550W | 998–1225 panels | 548.9–673.8 kW DC |
CEC-Listed 240V Equivalents to EPC Power 50-100A-BCDEF-G
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (499.13 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for EPC Power 50-100A-BCDEF-G
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 19–22 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 19–22 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575 | 575 W | 53.5 V | 19–21 per string (-10°C) | Verify Pair |
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 20–22 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 20–23 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 15–17 per string (-10°C) | Verify Pair |
Engineering FAQ — EPC Power 50-100A-BCDEF-G
What size circuit breaker does the EPC Power 50-100A-BCDEF-G require under NEC 705.12?
At 499.13 kW continuous AC output on 480V (600.4A continuous), the 125% continuous duty rule requires a minimum 800A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the EPC Power 50-100A-BCDEF-G?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 499.13 kW unit with 549.04 kW to 673.83 kW DC of solar modules without exceeding 1250V cold Voc.