EPC Power 50-200100 (273.231 kW)
273 kVA, 350 Vac 3 phase Grid Support Utility Interactive Battery Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
273.231 kW
CEC Weighted Eff.
98%
MPPT / Max DC
575–1200V / 1200V
NEC 705.12 Breaker
600A @ 350V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | EPC Power |
|---|---|
| Model Number (MPN) | 50-200100 |
| Inverter Topology | Commercial 3-Phase Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 273.231 kW (273,231 W) |
| Nominal DC Input (Pdco) | 279,799 W |
| Nominal AC Voltage | 350 Vac (3-Phase) |
| Listed Voltage Variants | 350V, 480V, 600V, 630V, 660V, 690V, 720V, 850V |
| CEC Weighted Efficiency | 98% |
| MPPT Operating Window | 575 – 1200 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 1200 Vdc |
| Max DC Input Current | 315.3 A |
| Night Tare Loss | Not reported in CEC |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | No |
| Certifying Laboratory | TUV Rheinland of North America |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 450.7 A @ 350V |
|---|---|
| 125% Continuous Duty Current | 563.4 A |
| Minimum Standard Breaker | 600 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (300.55–368.86 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 751–922 panels | 300.4–368.8 kW DC |
| 440W | 683–838 panels | 300.5–368.7 kW DC |
| 550W | 546–671 panels | 300.3–369.1 kW DC |
CEC-Listed 240V Equivalents to EPC Power 50-200100
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (273.231 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for EPC Power 50-200100
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 16–21 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 16–21 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575 | 575 W | 53.5 V | 16–20 per string (-10°C) | Verify Pair |
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 16–21 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 16–22 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 13–16 per string (-10°C) | Verify Pair |
Engineering FAQ — EPC Power 50-200100
What size circuit breaker does the EPC Power 50-200100 require under NEC 705.12?
At 273.231 kW continuous AC output on 350V (450.7A continuous), the 125% continuous duty rule requires a minimum 600A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the EPC Power 50-200100?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 273.231 kW unit with 300.55 kW to 368.86 kW DC of solar modules without exceeding 1200V cold Voc.