Ingeteam INGECON SUN 1245TL U B480 (1042.22 kW)
1247 kVA, 480 Vac Grid Support Utility Interactive Inverter for PV and Battery Applications. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
1042.22 kW
CEC Weighted Eff.
97.5%
MPPT / Max DC
697–1200V / 1200V
NEC 705.12 Breaker
1600A @ 480V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Ingeteam |
|---|---|
| Model Number (MPN) | INGECON SUN 1245TL U B480 |
| Inverter Topology | Commercial 3-Phase Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 1042.22 kW (1,042,220 W) |
| Nominal DC Input (Pdco) | 1,076,260 W |
| Nominal AC Voltage | 480 Vac (3-Phase) |
| CEC Weighted Efficiency | 97.5% |
| MPPT Operating Window | 697 – 1200 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 1200 Vdc |
| Max DC Input Current | 1134.1 A |
| Night Tare Loss | 459.07 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 1253.6 A @ 480V |
|---|---|
| 125% Continuous Duty Current | 1567.0 A |
| Minimum Standard Breaker | 1600 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (1146.44–1407 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 2866–3518 panels | 1146.4–1407.2 kW DC |
| 440W | 2606–3198 panels | 1146.6–1407.1 kW DC |
| 550W | 2084–2558 panels | 1146.2–1406.9 kW DC |
CEC-Listed 240V Equivalents to Ingeteam INGECON SUN 1245TL U B480
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (1042.22 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for Ingeteam INGECON SUN 1245TL U B480
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 19–21 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 19–21 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575 | 575 W | 53.5 V | 19–20 per string (-10°C) | Verify Pair |
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 20–21 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 20–22 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 15–16 per string (-10°C) | Verify Pair |
Engineering FAQ — Ingeteam INGECON SUN 1245TL U B480
What size circuit breaker does the Ingeteam INGECON SUN 1245TL U B480 require under NEC 705.12?
At 1042.22 kW continuous AC output on 480V (1253.6A continuous), the 125% continuous duty rule requires a minimum 1600A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Ingeteam INGECON SUN 1245TL U B480?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 1042.22 kW unit with 1146.44 kW to 1407 kW DC of solar modules without exceeding 1200V cold Voc.