Ingeteam INGECON SUN 915TL U B330 (915 kW)
915 kW, 330 Vac Grid Support Utility Interactive Inverter for PV and Battery Applications. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
915 kW
CEC Weighted Eff.
97.5%
MPPT / Max DC
485–740V / 740V
NEC 705.12 Breaker
2100A @ 330V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Ingeteam |
|---|---|
| Model Number (MPN) | INGECON SUN 915TL U B330 |
| Inverter Topology | Commercial 3-Phase Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 915 kW (915,000 W) |
| Nominal DC Input (Pdco) | 941,368 W |
| Nominal AC Voltage | 330 Vac (3-Phase) |
| CEC Weighted Efficiency | 97.5% |
| MPPT Operating Window | 485 – 740 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 740 Vdc |
| Max DC Input Current | 1535.7 A |
| Night Tare Loss | 80 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 1600.9 A @ 330V |
|---|---|
| 125% Continuous Duty Current | 2001.1 A |
| Minimum Standard Breaker | 2100 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (1006.5–1235.25 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 2516–3088 panels | 1006.4–1235.2 kW DC |
| 440W | 2288–2807 panels | 1006.7–1235.1 kW DC |
| 550W | 1830–2246 panels | 1006.5–1235.3 kW DC |
CEC-Listed 240V Equivalents to Ingeteam INGECON SUN 915TL U B330
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (915 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for Ingeteam INGECON SUN 915TL U B330
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 13–13 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 13–13 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-520MB-AG | 520 W | 48.4 V | 14–14 per string (-10°C) | Verify Pair |
| Trina Solar TSM-445NEG9RH.25 | 445 W | 35.7 V | 19–19 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.TRON BLK M-G2.D+ 445 | 445 W | 40.16 V | 17–17 per string (-10°C) | Verify Pair |
| Silfab Solar SIL-540XM | 540 W | 47.95 V | 14–14 per string (-10°C) | Verify Pair |
Engineering FAQ — Ingeteam INGECON SUN 915TL U B330
What size circuit breaker does the Ingeteam INGECON SUN 915TL U B330 require under NEC 705.12?
At 915 kW continuous AC output on 330V (1600.9A continuous), the 125% continuous duty rule requires a minimum 2100A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Ingeteam INGECON SUN 915TL U B330?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 915 kW unit with 1006.5 kW to 1235.25 kW DC of solar modules without exceeding 740V cold Voc.