LG Electronics / LG Energy P250KH53231 (250.425 kW)
250 kW, 480 Vac, Bi-directional, 3 phase Grid Support Utility Interactive Battery Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
250.425 kW
CEC Weighted Eff.
97%
MPPT / Max DC
750–1000V / 1000V
NEC 705.12 Breaker
400A @ 480V
Inverter Engineering Tools
Legacy / Replacement Reference: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | LG Electronics / LG Energy |
|---|---|
| Model Number (MPN) | P250KH53231 |
| Inverter Topology | Commercial 3-Phase Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 250.425 kW (250,425 W) |
| Nominal DC Input (Pdco) | 258,041 W |
| Nominal AC Voltage | 480 Vac (3-Phase) |
| CEC Weighted Efficiency | 97% |
| MPPT Operating Window | 750 – 1000 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 1000 Vdc |
| Max DC Input Current | 292.9 A |
| Night Tare Loss | 4.21 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 301.2 A @ 480V |
|---|---|
| 125% Continuous Duty Current | 376.5 A |
| Minimum Standard Breaker | 400 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (275.47–338.07 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 689–845 panels | 275.6–338.0 kW DC |
| 440W | 626–768 panels | 275.4–337.9 kW DC |
| 550W | 501–615 panels | 275.6–338.3 kW DC |
CEC-Listed 240V Equivalents to LG Electronics / LG Energy P250KH53231
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (250.425 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Engineering FAQ — LG Electronics / LG Energy P250KH53231
What size circuit breaker does the LG Electronics / LG Energy P250KH53231 require under NEC 705.12?
At 250.425 kW continuous AC output on 480V (301.2A continuous), the 125% continuous duty rule requires a minimum 400A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the LG Electronics / LG Energy P250KH53231?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 250.425 kW unit with 275.47 kW to 338.07 kW DC of solar modules without exceeding 1000V cold Voc.