Power Electronics FS1400CU15 (1517.09 kW)
1400 kW, 565 Vac Grid Support Utility Interactive Inverter with combiner box. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
1517.09 kW
CEC Weighted Eff.
97.5%
MPPT / Max DC
800–1200V / 1200V
NEC 705.12 Breaker
2000A @ 565V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Power Electronics |
|---|---|
| Model Number (MPN) | FS1400CU15 |
| Inverter Topology | Commercial 3-Phase Inverter |
| Continuous AC Power (Paco) | 1517.09 kW (1,517,090 W) |
| Nominal DC Input (Pdco) | 1,555,110 W |
| Nominal AC Voltage | 565 Vac (3-Phase) |
| CEC Weighted Efficiency | 97.5% |
| MPPT Operating Window | 800 – 1200 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 1200 Vdc |
| Max DC Input Current | 1727.9 A |
| Night Tare Loss | 359.56 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 1550.3 A @ 565V |
|---|---|
| 125% Continuous Duty Current | 1937.9 A |
| Minimum Standard Breaker | 2000 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (1668.8–2048.07 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 4172–5120 panels | 1668.8–2048.0 kW DC |
| 440W | 3793–4655 panels | 1668.9–2048.2 kW DC |
| 550W | 3034–3724 panels | 1668.7–2048.2 kW DC |
CEC-Listed 240V Equivalents to Power Electronics FS1400CU15
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (1517.09 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for Power Electronics FS1400CU15
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 21–21 per string (-10°C) | Verify Pair |
| SEG Solar SEG-545-BTC-BG | 545 W | 48.2 V | 23–23 per string (-10°C) | Verify Pair |
| Canadian Solar CS6.2-48TM-460H | 460 W | 36.2 V | 31–31 per string (-10°C) | Verify Pair |
| Silfab Solar SIL-540QM | 540 W | 47.96 V | 23–23 per string (-10°C) | Verify Pair |
| Maxeon / SunPower SPR-MAX6-445 | 445 W | 48.2 V | 23–23 per string (-10°C) | Verify Pair |
| REC Solar REC430AA Pure 2 | 430 W | 49 V | 22–22 per string (-10°C) | Verify Pair |
Engineering FAQ — Power Electronics FS1400CU15
What size circuit breaker does the Power Electronics FS1400CU15 require under NEC 705.12?
At 1517.09 kW continuous AC output on 565V (1550.3A continuous), the 125% continuous duty rule requires a minimum 2000A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Power Electronics FS1400CU15?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 1517.09 kW unit with 1668.8 kW to 2048.07 kW DC of solar modules without exceeding 1200V cold Voc.