Power Electronics FS1475CU15 (1610.37 kW)
1475 kW, 600 Vac Grid Support Utility Interactive Inverter with combiner box. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
1610.37 kW
CEC Weighted Eff.
97.5%
MPPT / Max DC
849–1200V / 1200V
NEC 705.12 Breaker
2000A @ 600V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Power Electronics |
|---|---|
| Model Number (MPN) | FS1475CU15 |
| Inverter Topology | Commercial 3-Phase Inverter |
| Continuous AC Power (Paco) | 1610.37 kW (1,610,370 W) |
| Nominal DC Input (Pdco) | 1,650,030 W |
| Nominal AC Voltage | 600 Vac (3-Phase) |
| CEC Weighted Efficiency | 97.5% |
| MPPT Operating Window | 849 – 1200 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 1200 Vdc |
| Max DC Input Current | 1755.4 A |
| Night Tare Loss | 368.71 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 1549.6 A @ 600V |
|---|---|
| 125% Continuous Duty Current | 1937.0 A |
| Minimum Standard Breaker | 2000 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (1771.41–2174 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 4429–5435 panels | 1771.6–2174.0 kW DC |
| 440W | 4026–4941 panels | 1771.4–2174.0 kW DC |
| 550W | 3221–3953 panels | 1771.5–2174.2 kW DC |
CEC-Listed 240V Equivalents to Power Electronics FS1475CU15
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (1610.37 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Engineering FAQ — Power Electronics FS1475CU15
What size circuit breaker does the Power Electronics FS1475CU15 require under NEC 705.12?
At 1610.37 kW continuous AC output on 600V (1549.6A continuous), the 125% continuous duty rule requires a minimum 2000A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Power Electronics FS1475CU15?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 1610.37 kW unit with 1771.41 kW to 2174 kW DC of solar modules without exceeding 1200V cold Voc.