Power Electronics FS2180K (2259.5 kW)
2255 kW, 615 Vac Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
2259.5 kW
CEC Weighted Eff.
98%
MPPT / Max DC
870–1200V / 1200V
NEC 705.12 Breaker
2700A @ 615V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Power Electronics |
|---|---|
| Model Number (MPN) | FS2180K |
| Inverter Topology | Commercial 3-Phase Inverter |
| Continuous AC Power (Paco) | 2259.5 kW (2,259,500 W) |
| Nominal DC Input (Pdco) | 2,304,420 W |
| Nominal AC Voltage | 615 Vac (3-Phase) |
| CEC Weighted Efficiency | 98% |
| MPPT Operating Window | 870 – 1200 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 1200 Vdc |
| Max DC Input Current | 2425.7 A |
| Night Tare Loss | 302.3 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 2121.2 A @ 615V |
|---|---|
| 125% Continuous Duty Current | 2651.5 A |
| Minimum Standard Breaker | 2700 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (2485.45–3050.33 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 6214–7626 panels | 2485.6–3050.4 kW DC |
| 440W | 5649–6933 panels | 2485.6–3050.5 kW DC |
| 550W | 4519–5546 panels | 2485.4–3050.3 kW DC |
CEC-Listed 240V Equivalents to Power Electronics FS2180K
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (2259.5 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Engineering FAQ — Power Electronics FS2180K
What size circuit breaker does the Power Electronics FS2180K require under NEC 705.12?
At 2259.5 kW continuous AC output on 615V (2121.2A continuous), the 125% continuous duty rule requires a minimum 2700A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Power Electronics FS2180K?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 2259.5 kW unit with 2485.45 kW to 3050.33 kW DC of solar modules without exceeding 1200V cold Voc.