Princeton Power Systems GTIB-480-125XXXXXX-G1.5 (124.964 kW)

125 kVA, 480 Vac, 830Vdc, Transformerless, Non-isolated, Grid Support Utility Interactive PV or Battery Inverter; where X can be -B, -D, -DH, -DA, -DD, -GN, -M, -OV, -V, or blank. Cannot accept PV and Battery DC input simultaneously. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .

Continuous AC Output
124.964 kW
CEC Weighted Eff.
96%
MPPT / Max DC
350–830V / 830V
NEC 705.12 Breaker
200A @ 480V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Princeton Power Systems GTIB-480-125XXXXXX-G1.5 — Illustrative category photo — not this exact model · Real commercial solar inverter installation
Illustrative category photo — not this exact model · Real commercial solar inverter installationWikimedia Commons — File:Central inverter cutout.jpg (CC0)
DC INPUT & MPPT TRACKING WINDOW (HYBRID) MPPT 350–830 Vdc 350V 830V MAX 830V PV DC INPUT ≤ 830V DC 124.964 kW · 96% CEC PV + BATTERY HYBRID AC OUTPUT 480V · 200A BRKR

Electrical & Grid-Support Datasheet

Princeton Power Systems GTIB-480-125XXXXXX-G1.5 Electrical and Grid-Support Specifications
ManufacturerPrinceton Power Systems
Model Number (MPN)GTIB-480-125XXXXXX-G1.5
Inverter TopologyCommercial 3-Phase Inverter (PV + Battery Hybrid)
Continuous AC Power (Paco)124.964 kW (124,964 W)
Nominal DC Input (Pdco)129,454 W
Nominal AC Voltage480 Vac (3-Phase)
CEC Weighted Efficiency96%
MPPT Operating Window350 – 830 Vdc (NREL SAM Measured)
Max DC Input Voltage830 Vdc
Max DC Input Current182.3 A
Night Tare Loss68 W
UL 1741 Supplement SBNo / Non-US
UL 1741 Supplement SACertified
Certifying LaboratoryNot listed in CEC
Built-in Revenue MeterNo / Optional

NEC 705.12(B) Backfeed & Panel Check

NEC 705.12 Backfeed Breaker Calculation for GTIB-480-125XXXXXX-G1.5
Max Continuous AC Current150.3 A @ 480V
125% Continuous Duty Current187.9 A
Minimum Standard Breaker200 A
Busbar RequirementSupply-Side Tap (NEC 705.11) or 400A/Commercial Service

Recommended PV Array Pairing

Target DC/AC ratio 1.10×–1.35× (137.46–168.7 kW DC total).

Recommended Solar Panel Quantity by Wattage Class for GTIB-480-125XXXXXX-G1.5
Panel ClassRecommended QtyDC Array / Ratio
400W344–422 panels137.6–168.8 kW DC
440W312–383 panels137.3–168.5 kW DC
550W250–307 panels137.5–168.8 kW DC

CEC-Listed 240V Equivalents to Princeton Power Systems GTIB-480-125XXXXXX-G1.5

Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (124.964 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:

CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid

Isuna U20K-PH

CEC Efficiency: 97%
Datasheet →
CEC-Listed · 240V19.378 kW
Base Power · Hybrid

000599.XX.Y

CEC Efficiency: 96%
Datasheet →
CEC-Listed · 240V17.944 kW
SRNE Solar · Hybrid

HEBP48180U380-H

CEC Efficiency: 96.5%
Datasheet →

Compatible Solar Panels for Princeton Power Systems GTIB-480-125XXXXXX-G1.5

Test any of 3,007 panels with this inverter →
Compatible Solar Panels for Princeton Power Systems GTIB-480-125XXXXXX-G1.5
Solar Panel ModelSTC PowerVoc (25°C)String / Pairing FitAction
Boviet Solar BVM7612M-580-H-HC-BF580 W52.42 V10–14 per string (-10°C)Verify Pair
SEG Solar SEG-580-BTA-HV580 W51.95 V10–14 per string (-10°C)Verify Pair
Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575575 W53.5 V10–14 per string (-10°C)Verify Pair
Mission Solar MSH10-560HN4G {A}560 W50.5 V10–15 per string (-10°C)Verify Pair
Canadian Solar CS6W-555MB-AG555 W49.8 V10–15 per string (-10°C)Verify Pair
REC Solar REC475AA Pure-RX-DC475 W65.7 V8–11 per string (-10°C)Verify Pair

Engineering FAQ — Princeton Power Systems GTIB-480-125XXXXXX-G1.5

What size circuit breaker does the Princeton Power Systems GTIB-480-125XXXXXX-G1.5 require under NEC 705.12?
At 124.964 kW continuous AC output on 480V (150.3A continuous), the 125% continuous duty rule requires a minimum 200A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Princeton Power Systems GTIB-480-125XXXXXX-G1.5?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 124.964 kW unit with 137.46 kW to 168.7 kW DC of solar modules without exceeding 830V cold Voc.

More Princeton Power Systems Inverters

GTIB-480-125XXXXXX-W-G1.5 (124.964 kW)GTIB-480-30-WZZZZZZ-G1.3 (29.444 kW)GTIB-480-30-ZZZZZZ-G1.3 (29.956 kW)All Princeton Power Systems Equipment →