Princeton Power Systems GTIB-480-30-WZZZZZZ-G1.3 (29.444 kW)
30 kVA, 480 Vac, 830Vdc, Non-isolated, Bi-directional, Grid Support Utility Interactive PV or Battery Inverter; where Z can be -ATS, -GA, -F, -GN-W-H, -H, -EMOS, or blank. Cannot accept PV and Battery DC input simultaneously. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
29.444 kW
CEC Weighted Eff.
93.5%
MPPT / Max DC
540–830V / 830V
NEC 705.12 Breaker
45A @ 480V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Princeton Power Systems |
|---|---|
| Model Number (MPN) | GTIB-480-30-WZZZZZZ-G1.3 |
| Inverter Topology | Commercial 3-Phase Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 29.444 kW (29,444 W) |
| Nominal DC Input (Pdco) | 31,735 W |
| Nominal AC Voltage | 480 Vac (3-Phase) |
| CEC Weighted Efficiency | 93.5% |
| MPPT Operating Window | 540 – 830 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 830 Vdc |
| Max DC Input Current | 42.3 A |
| Night Tare Loss | 35.14 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 35.4 A @ 480V |
|---|---|
| 125% Continuous Duty Current | 44.3 A |
| Minimum Standard Breaker | 45 A |
| Busbar Requirement | 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (32.39–39.75 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 81–99 panels | 32.4–39.6 kW DC |
| 440W | 74–90 panels | 32.6–39.6 kW DC |
| 550W | 59–72 panels | 32.5–39.6 kW DC |
CEC-Listed 240V Equivalents to Princeton Power Systems GTIB-480-30-WZZZZZZ-G1.3
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (29.444 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for Princeton Power Systems GTIB-480-30-WZZZZZZ-G1.3
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 15–15 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 15–15 per string (-10°C) | Verify Pair |
| SEG Solar SEG-535-BTC-HV | 535 W | 47.81 V | 16–16 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.TRON BLK M-G2.D+ 445 | 445 W | 40.16 V | 19–19 per string (-10°C) | Verify Pair |
| Silfab Solar SIL-515XM | 515 W | 47.41 V | 16–16 per string (-10°C) | Verify Pair |
| Boviet Solar BVM7610M-490-H-HC-BF | 490 W | 44.58 V | 17–17 per string (-10°C) | Verify Pair |
Engineering FAQ — Princeton Power Systems GTIB-480-30-WZZZZZZ-G1.3
What size circuit breaker does the Princeton Power Systems GTIB-480-30-WZZZZZZ-G1.3 require under NEC 705.12?
At 29.444 kW continuous AC output on 480V (35.4A continuous), the 125% continuous duty rule requires a minimum 45A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the Princeton Power Systems GTIB-480-30-WZZZZZZ-G1.3?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 29.444 kW unit with 32.39 kW to 39.75 kW DC of solar modules without exceeding 830V cold Voc.