Schneider Electric CS2200-NA (2200 kW)

2.2 MW, 1500 Vdc, 600 Vac, 3-phase, Special Purpose Grid Support Utility Interactive PV Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .

Continuous AC Output
2200 kW
CEC Weighted Eff.
98%
MPPT / Max DC
905–1200V / 1200V
NEC 705.12 Breaker
2700A @ 600V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Schneider Electric CS2200-NA — Illustrative category photo — not this exact model · Real commercial solar inverter installation
Illustrative category photo — not this exact model · Real commercial solar inverter installationWikimedia Commons — File:Central inverter cutout.jpg (CC0)
DC INPUT & MPPT TRACKING WINDOW (STRING) MPPT 905–1200 Vdc 905V 1200V MAX 1200V PV DC INPUT ≤ 1200V DC 2200 kW · 98% CEC GRID-SUPPORT INVERTER AC OUTPUT 600V · 2700A BRKR

Electrical & Grid-Support Datasheet

Schneider Electric CS2200-NA Electrical and Grid-Support Specifications
ManufacturerSchneider Electric
Model Number (MPN)CS2200-NA
Inverter TopologyCommercial 3-Phase Inverter
Continuous AC Power (Paco)2200 kW (2,200,000 W)
Nominal DC Input (Pdco)2,263,730 W
Nominal AC Voltage600 Vac (3-Phase)
CEC Weighted Efficiency98%
MPPT Operating Window905 – 1200 Vdc (NREL SAM Measured)
Max DC Input Voltage1200 Vdc
Max DC Input Current2147.8 A
Night Tare Loss295 W
UL 1741 Supplement SBNo / Non-US
UL 1741 Supplement SACertified
Certifying LaboratoryNot listed in CEC
Built-in Revenue MeterNo / Optional

NEC 705.12(B) Backfeed & Panel Check

NEC 705.12 Backfeed Breaker Calculation for CS2200-NA
Max Continuous AC Current2117 A @ 600V
125% Continuous Duty Current2646.3 A
Minimum Standard Breaker2700 A
Busbar RequirementSupply-Side Tap (NEC 705.11) or 400A/Commercial Service

Recommended PV Array Pairing

Target DC/AC ratio 1.10×–1.35× (2420–2970 kW DC total).

Recommended Solar Panel Quantity by Wattage Class for CS2200-NA
Panel ClassRecommended QtyDC Array / Ratio
400W6050–7425 panels2420.0–2970.0 kW DC
440W5500–6750 panels2420.0–2970.0 kW DC
550W4400–5400 panels2420.0–2970.0 kW DC

CEC-Listed 240V Equivalents to Schneider Electric CS2200-NA

Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (2200 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:

CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid

Isuna U20K-PH

CEC Efficiency: 97%
Datasheet →
CEC-Listed · 240V19.378 kW
Base Power · Hybrid

000599.XX.Y

CEC Efficiency: 96%
Datasheet →
CEC-Listed · 240V17.944 kW
SRNE Solar · Hybrid

HEBP48180U380-H

CEC Efficiency: 96.5%
Datasheet →

Engineering FAQ — Schneider Electric CS2200-NA

What size circuit breaker does the Schneider Electric CS2200-NA require under NEC 705.12?
At 2200 kW continuous AC output on 600V (2117A continuous), the 125% continuous duty rule requires a minimum 2700A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Schneider Electric CS2200-NA?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 2200 kW unit with 2420 kW to 2970 kW DC of solar modules without exceeding 1200V cold Voc.