Sigenergy SigenStor EC 7.6 SP US (7.649 kW)
7.6 kW, 240 Vac Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
7.649 kW
CEC Weighted Eff.
97%
MPPT / Max DC
270–480V / 480V
NEC 705.12 Breaker
40A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Electrical & Grid-Support Datasheet
| Manufacturer | Sigenergy |
|---|---|
| Model Number (MPN) | SigenStor EC 7.6 SP US |
| Inverter Topology | Hybrid Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 7.649 kW (7,649 W) |
| Nominal DC Input (Pdco) | 7,893 W |
| Nominal AC Voltage | 240 Vac (Split/Single-Phase) |
| CEC Weighted Efficiency | 97% |
| MPPT Operating Window | 270 – 480 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 480 Vdc |
| Max DC Input Current | 21.9 A |
| Night Tare Loss | 3.3 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | No |
| Certifying Laboratory | CSA Group |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 31.9 A @ 240V |
|---|---|
| 125% Continuous Duty Current | 39.9 A |
| Minimum Standard Breaker | 40 A |
| Busbar Requirement | 200A Busbar (120% rule: up to 40A backfeed) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (8.41–10.33 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 21–26 panels | 8.4–10.4 kW DC |
| 440W | 19–23 panels | 8.4–10.1 kW DC |
| 550W | 15–19 panels | 8.3–10.4 kW DC |
Compatible Solar Panels for Sigenergy SigenStor EC 7.6 SP US
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 8–8 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 8–8 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575 | 575 W | 53.5 V | 8–8 per string (-10°C) | Verify Pair |
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 8–8 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 8–8 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 6–6 per string (-10°C) | Verify Pair |
Engineering FAQ — Sigenergy SigenStor EC 7.6 SP US
What size circuit breaker does the Sigenergy SigenStor EC 7.6 SP US require under NEC 705.12?
At 7.649 kW continuous AC output on 240V (31.9A continuous), the 125% continuous duty rule requires a minimum 40A overcurrent breaker. Busbar note: 200A Busbar (120% rule: up to 40A backfeed).
What solar array size pairs best with the Sigenergy SigenStor EC 7.6 SP US?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 7.649 kW unit with 8.41 kW to 10.33 kW DC of solar modules without exceeding 480V cold Voc.