SolarEdge SE6000H-US (6.046 kW)
6 kW, 240 Vac, 1-phase, HD-Wave technology hybrid Grid Support Utility Interactive Inverter, with PCS functionality. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
6.046 kW
CEC Weighted Eff.
99%
MPPT / Max DC
360–480V / 480V
NEC 705.12 Breaker
35A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Electrical & Grid-Support Datasheet
| Manufacturer | SolarEdge |
|---|---|
| Model Number (MPN) | SE6000H-US |
| Inverter Topology | Hybrid Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 6.046 kW (6,046 W) |
| Nominal DC Input (Pdco) | 6,113 W |
| Nominal AC Voltage | 240 Vac (Split/Single-Phase) |
| Listed Voltage Variants | 208V, 240V |
| CEC Weighted Efficiency | 99% |
| MPPT Operating Window | 360 – 480 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 480 Vdc |
| Max DC Input Current | 15.5 A |
| Night Tare Loss | 4.52 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Intertek |
| Built-in Revenue Meter | Yes |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 25.2 A @ 240V |
|---|---|
| 125% Continuous Duty Current | 31.5 A |
| Minimum Standard Breaker | 35 A |
| Busbar Requirement | 200A Busbar (120% rule: up to 40A backfeed) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (6.65–8.16 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 17–20 panels | 6.8–8.0 kW DC |
| 440W | 15–19 panels | 6.6–8.4 kW DC |
| 550W | 12–15 panels | 6.6–8.3 kW DC |
Engineering FAQ — SolarEdge SE6000H-US
What size circuit breaker does the SolarEdge SE6000H-US require under NEC 705.12?
At 6.046 kW continuous AC output on 240V (25.2A continuous), the 125% continuous duty rule requires a minimum 35A overcurrent breaker. Busbar note: 200A Busbar (120% rule: up to 40A backfeed).
What solar array size pairs best with the SolarEdge SE6000H-US?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 6.046 kW unit with 6.65 kW to 8.16 kW DC of solar modules without exceeding 480V cold Voc.