Solis (Ginlong) 100K-EHV-5G (100 kW)
100 kW, 600 Vac, 3-phase Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
100 kW
CEC Weighted Eff.
98.5%
MPPT / Max DC
860–1250V / 1250V
NEC 705.12 Breaker
125A @ 600V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Solis (Ginlong) |
|---|---|
| Model Number (MPN) | 100K-EHV-5G |
| Inverter Topology | Commercial 3-Phase Inverter |
| Continuous AC Power (Paco) | 100 kW (100,000 W) |
| Nominal DC Input (Pdco) | 101,429 W |
| Nominal AC Voltage | 600 Vac (3-Phase) |
| CEC Weighted Efficiency | 98.5% |
| MPPT Operating Window | 860 – 1250 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 1250 Vdc |
| Max DC Input Current | 106.8 A |
| Night Tare Loss | 1 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 96.2 A @ 600V |
|---|---|
| 125% Continuous Duty Current | 120.3 A |
| Minimum Standard Breaker | 125 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (110–135 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 275–338 panels | 110.0–135.2 kW DC |
| 440W | 250–307 panels | 110.0–135.1 kW DC |
| 550W | 200–245 panels | 110.0–134.8 kW DC |
CEC-Listed 240V Equivalents to Solis (Ginlong) 100K-EHV-5G
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (100 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Engineering FAQ — Solis (Ginlong) 100K-EHV-5G
What size circuit breaker does the Solis (Ginlong) 100K-EHV-5G require under NEC 705.12?
At 100 kW continuous AC output on 600V (96.2A continuous), the 125% continuous duty rule requires a minimum 125A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Solis (Ginlong) 100K-EHV-5G?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 100 kW unit with 110 kW to 135 kW DC of solar modules without exceeding 1250V cold Voc.