Solis (Ginlong) 50K-US-F-LSW (49.916 kW)
50 kW, 480 Vac Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
49.916 kW
CEC Weighted Eff.
98.5%
MPPT / Max DC
568–850V / 850V
NEC 705.12 Breaker
80A @ 480V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Solis (Ginlong) |
|---|---|
| Model Number (MPN) | 50K-US-F-LSW |
| Inverter Topology | Commercial 3-Phase Inverter |
| Continuous AC Power (Paco) | 49.916 kW (49,916 W) |
| Nominal DC Input (Pdco) | 50,766 W |
| Nominal AC Voltage | 480 Vac (3-Phase) |
| CEC Weighted Efficiency | 98.5% |
| MPPT Operating Window | 568 – 850 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 850 Vdc |
| Max DC Input Current | 70.5 A |
| Night Tare Loss | 1 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 60 A @ 480V |
|---|---|
| 125% Continuous Duty Current | 75.0 A |
| Minimum Standard Breaker | 80 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (54.91–67.39 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 137–168 panels | 54.8–67.2 kW DC |
| 440W | 125–153 panels | 55.0–67.3 kW DC |
| 550W | 100–123 panels | 55.0–67.7 kW DC |
CEC-Listed 240V Equivalents to Solis (Ginlong) 50K-US-F-LSW
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (49.916 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for Solis (Ginlong) 50K-US-F-LSW
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 15–15 per string (-10°C) | Verify Pair |
| SEG Solar SEG-560-BTC-HV | 560 W | 48.81 V | 16–16 per string (-10°C) | Verify Pair |
| Silfab Solar SIL-540XM | 540 W | 47.95 V | 16–16 per string (-10°C) | Verify Pair |
| Canadian Solar CS6.2-48TM-460H | 460 W | 36.2 V | 22–22 per string (-10°C) | Verify Pair |
| REC Solar REC430AA Pure 2 | 430 W | 49 V | 16–16 per string (-10°C) | Verify Pair |
| Maxeon / SunPower SPR-MAX3-435-COM-R | 435 W | 40.7 V | 19–19 per string (-10°C) | Verify Pair |
Engineering FAQ — Solis (Ginlong) 50K-US-F-LSW
What size circuit breaker does the Solis (Ginlong) 50K-US-F-LSW require under NEC 705.12?
At 49.916 kW continuous AC output on 480V (60A continuous), the 125% continuous duty rule requires a minimum 80A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Solis (Ginlong) 50K-US-F-LSW?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 49.916 kW unit with 54.91 kW to 67.39 kW DC of solar modules without exceeding 850V cold Voc.