Solis (Ginlong) 75K-5G-US (75 kW)
75 kW, 480 Vac, 3-Phase Transformerless Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
75 kW
CEC Weighted Eff.
98.5%
MPPT / Max DC
550–850V / 850V
NEC 705.12 Breaker
125A @ 480V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Solis (Ginlong) |
|---|---|
| Model Number (MPN) | 75K-5G-US |
| Inverter Topology | Commercial 3-Phase Inverter |
| Continuous AC Power (Paco) | 75 kW (75,000 W) |
| Nominal DC Input (Pdco) | 76,332 W |
| Nominal AC Voltage | 480 Vac (3-Phase) |
| CEC Weighted Efficiency | 98.5% |
| MPPT Operating Window | 550 – 850 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 850 Vdc |
| Max DC Input Current | 106 A |
| Night Tare Loss | 1 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 90.2 A @ 480V |
|---|---|
| 125% Continuous Duty Current | 112.8 A |
| Minimum Standard Breaker | 125 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (82.5–101.25 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 206–253 panels | 82.4–101.2 kW DC |
| 440W | 188–230 panels | 82.7–101.2 kW DC |
| 550W | 150–184 panels | 82.5–101.2 kW DC |
CEC-Listed 240V Equivalents to Solis (Ginlong) 75K-5G-US
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (75 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for Solis (Ginlong) 75K-5G-US
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 15–15 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 15–15 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-520MB-AG | 520 W | 48.4 V | 16–16 per string (-10°C) | Verify Pair |
| Trina Solar TSM-460NEG9RH.25 | 460 W | 36.3 V | 21–21 per string (-10°C) | Verify Pair |
| Mission Solar MSX10-445HN0B {C} | 445 W | 38.7 V | 20–20 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.TRON BLK M-G2.D+ 415 | 415 W | 38.47 V | 20–20 per string (-10°C) | Verify Pair |
Engineering FAQ — Solis (Ginlong) 75K-5G-US
What size circuit breaker does the Solis (Ginlong) 75K-5G-US require under NEC 705.12?
At 75 kW continuous AC output on 480V (90.2A continuous), the 125% continuous duty rule requires a minimum 125A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Solis (Ginlong) 75K-5G-US?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 75 kW unit with 82.5 kW to 101.25 kW DC of solar modules without exceeding 850V cold Voc.