CEC-Listed · Commercial / C&IHybridUL 1741-SB (3rd Ed.)Battery HybridEstimated MPPT — Verify Manufacturer Datasheet
SRNE Solar SEI-16K-U3P (16.064 kW)
16 kW, 208 Vac Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
16.064 kW
CEC Weighted Eff.
97%
MPPT / Max DC
120–500V / 600VEstimated MPPT — Verify Datasheet
NEC 705.12 Breaker
60A @ 208V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | SRNE Solar |
|---|---|
| Model Number (MPN) | SEI-16K-U3P |
| Inverter Topology | Hybrid Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 16.064 kW (16,064 W) |
| Nominal DC Input (Pdco) | 16,561 W |
| Nominal AC Voltage | 208 Vac (3-Phase) |
| CEC Weighted Efficiency | 97% |
| MPPT Operating Window | 120 – 500 Vdc (Nominal Class Estimate (Verify Datasheet))Estimated MPPT — Verify Manufacturer Datasheet before string design |
| Max DC Input Voltage | 600 Vdc |
| Max DC Input Current | 51.3 A |
| Night Tare Loss | 37.19 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | No |
| Certifying Laboratory | Intertek |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 44.6 A @ 208V |
|---|---|
| 125% Continuous Duty Current | 55.8 A |
| Minimum Standard Breaker | 60 A |
| Busbar Requirement | 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (17.67–21.69 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 44–54 panels | 17.6–21.6 kW DC |
| 440W | 40–49 panels | 17.6–21.6 kW DC |
| 550W | 32–39 panels | 17.6–21.4 kW DC |
CEC-Listed 240V Equivalents to SRNE Solar SEI-16K-U3P
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (16.064 kW Hybrid Inverter) and can be added directly to your US System Kit:
Compatible Solar Panels for SRNE Solar SEI-16K-U3P
Test any of 3,007 panels with this inverter →Estimated MPPT — Verify Manufacturer DatasheetThis inverter’s MPPT window (120–500 Vdc) is a topology estimate because the CEC file did not list explicit MPPT bounds. Confirm exact startup and MPPT voltage limits on the manufacturer datasheet before finalizing string lengths.
| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 4–10 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 4–10 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575 | 575 W | 53.5 V | 4–10 per string (-10°C) | Verify Pair |
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 4–10 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 4–11 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 3–8 per string (-10°C) | Verify Pair |
Engineering FAQ — SRNE Solar SEI-16K-U3P
What size circuit breaker does the SRNE Solar SEI-16K-U3P require under NEC 705.12?
At 16.064 kW continuous AC output on 208V (44.6A continuous), the 125% continuous duty rule requires a minimum 60A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the SRNE Solar SEI-16K-U3P?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 16.064 kW unit with 17.67 kW to 21.69 kW DC of solar modules without exceeding 600V cold Voc.