Tesla Energy 1534000-xx-y (3.8 kW)
3.8 kW, 240 Vac Grid Support Utility Interactive Inverter, where xx is two numbers and y is a letter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
3.8 kW
CEC Weighted Eff.
97.5%
MPPT / Max DC
270–425V / 425V
NEC 705.12 Breaker
20A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Electrical & Grid-Support Datasheet
| Manufacturer | Tesla Energy |
|---|---|
| Model Number (MPN) | 1534000-xx-y |
| Inverter Topology | String Inverter |
| Continuous AC Power (Paco) | 3.8 kW (3,800 W) |
| Nominal DC Input (Pdco) | 3,893 W |
| Nominal AC Voltage | 240 Vac (Split/Single-Phase) |
| Listed Voltage Variants | 208V, 240V |
| CEC Weighted Efficiency | 97.5% |
| MPPT Operating Window | 270 – 425 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 425 Vdc |
| Max DC Input Current | 11.1 A |
| Night Tare Loss | 4.66 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Intertek |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 15.8 A @ 240V |
|---|---|
| 125% Continuous Duty Current | 19.8 A |
| Minimum Standard Breaker | 20 A |
| Busbar Requirement | 100A Busbar (120% rule: up to 20A backfeed) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (4.18–5.13 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 10–13 panels | 4.0–5.2 kW DC |
| 440W | 10–12 panels | 4.4–5.3 kW DC |
| 550W | 8–9 panels | 4.4–5.0 kW DC |
Compatible Solar Panels for Tesla Energy 1534000-xx-y
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| SEG Solar SEG-560-BTC-HV | 560 W | 48.81 V | 8–8 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-520MB-AG | 520 W | 48.4 V | 8–8 per string (-10°C) | Verify Pair |
| Mission Solar MSX10-445HN0B {C} | 445 W | 38.7 V | 10–10 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.TRON BLK M-G2.D+ 415 | 415 W | 38.47 V | 10–10 per string (-10°C) | Verify Pair |
| Silfab Solar SIL-540XM | 540 W | 47.95 V | 8–8 per string (-10°C) | Verify Pair |
| Boviet Solar BVM7610M-455-H-HC-BF | 455 W | 43.25 V | 9–9 per string (-10°C) | Verify Pair |
Engineering FAQ — Tesla Energy 1534000-xx-y
What size circuit breaker does the Tesla Energy 1534000-xx-y require under NEC 705.12?
At 3.8 kW continuous AC output on 240V (15.8A continuous), the 125% continuous duty rule requires a minimum 20A overcurrent breaker. Busbar note: 100A Busbar (120% rule: up to 20A backfeed).
What solar array size pairs best with the Tesla Energy 1534000-xx-y?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 3.8 kW unit with 4.18 kW to 5.13 kW DC of solar modules without exceeding 425V cold Voc.